EasyManuals Logo
Home>ABB>Controller>AC 800F

ABB AC 800F User Manual

ABB AC 800F
379 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #313 background imageLoading...
Page #313 background image
9 Technical Data of the AC 800F
9-3
9.4 Safety specifications
The requirements of EC regulation 73/23/EEC (low voltage regulation) and of CSA/UL
are met.
Class of equipment II
Do not connect a protective ground conductor!
Overvoltage category II for all connectors, pollution degree 2
Design to IEC 1010-1 (1990 - 09); EN 61010-1 / 3.94 or
DIN/EN 61010 - Part 1 / 3.94 (VDE 0411 - Part 1);
CSAC 22.2, No. 1010-1
,
SIQ (CB Scheme 97NK2421), CSA/NTRL; CSA/FM
Supply of modules extra low voltage with protective separation from
other circuits which may be earthed according to IEC
364-4-41:1991
Power supply module
SA 801F and SA 811F Safety isolating transformer according to EN 60742
Optocoupler for protective separation against
electrical shock (German standard VDE 0884 / 8.87)
Power supply module
SD 802F and SD 812F No el. separation !
Do not connect to any other voltage than the extra low voltage with
protective separation from other circuits to IEC 364-4-41:10.1992.