ABB i-bus
®
KNX
Parameters
218 2CDC508198D0211 Rev. A | AC/S 1.x.1
7.7.5 BACnet objects
Type
Object name
Object type
Unit
COV send
condition
Output Room: Actual room temperature Analog value °C (62) 1.0
Output Room: Room setpoint temperature Analog value °C (62) 1.0
Output
Room: Controller On/Off
Binary value
-
-
Output
Room: Heating/cooling operating type
Binary value
-
-
Output
Room: Operating mode
Positive integer
value
No unit (95)
1.0
Output
Room: Operating mode override (slave)
Positive integer
value
No unit (95)
1.0
Output Room: Window status Binary value - -
Output Room: Presence (slave) Binary value - -
Output
Room: Rel. humidity value
Analog value
% (98)
1.0
Output
Room: CO2 value
Analog value
ppm (96)
1.0
Output
Room: Fan coil unit, valve heating
Analog value
% (98)
1.0
Output
Room: Fan coil unit, valve cooling
Analog value
% (98)
1.0
Output Room: Fan coil unit, valve Analog value % (98) 1.0
Output Room: Fan coil unit, fan speed Analog value % (98) 1.0
Output Room: Fan coil unit, fan manual Binary value - -
Output Room: Fan coil unit, additional-stage heating Binary value
Analog value
-
% (98)
-
1.0
Output Room: Fan coil unit, fresh air damper Binary value
Analog value
-
% (98)
-
1.0
Output
Room: Fan coil unit, dew point sensor
Binary value
-
-
Output
Room: Fan coil unit, level sensor
Binary value
-
-
Output Room: Radiator, valve Binary value
Analog value
-
% (98)
-
1.0
Output
Room: Floor heating, valve
Binary value
Analog value
-
% (98)
-
1.0
Output
Room: Floor temperature sensor
Analog value
°C (62)
1.0
Output
Room: Cooling ceiling, valve
Binary value
Analog value
-
% (98)
-
1.0
Output Room: Cooling ceiling, dew point alarm sensor Binary value - -
Output
Room: Split unit, On/Off
Binary value
-
-
Output
Room: Split unit, fan speed
Analog value
% (98)
1.0
Output
Room: Split unit, status
Positive integer
value
No unit (95)
1.0
BACnet input objects
None

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB i-bus KNX AC/S 1.x.1 Series and is the answer not in the manual?

ABB i-bus KNX AC/S 1.x.1 Series Specifications

General IconGeneral
BrandABB
Modeli-bus KNX AC/S 1.x.1 Series
CategoryController
LanguageEnglish

Related product manuals