ABB i-bus
®
KNX
Parameters
446 2CDC508198D0211 Rev. A | AC/S 1.x.1
7.17.5 BACnet objects
Type
BACnet name
Object type
Unit
COV send
condition
Input ON/OFF Scheduler BACnet: State Schedule - -
Input ON/OFF Scheduler BACnet: Calendar Calendar - -
BACnet input objects
Object name
Object type
Unit
COV send
condition
Operating mode Scheduler BACnet: State
Schedule
Multistate
-
Use this BACnet object of type Schedule to parametrize the switching times with the related operating types via BACnet.
Signal value:
1 = Comfort
2 = Standby
3 = Economy
4 = Building Protection
Operating mode Scheduler BACnet: Calendar Calendar - -
The module has this BACnet input object if the
Yes
option is selected for the
Activated
parameter in
Calendar
section of the
BACnet parameter window.
This BACnet calendar object can be used to define an additional exception calendar and to link this to any BACnet scheduler
in the BACnet system.
BACnet output objects
None

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB i-bus KNX AC/S 1.x.1 Series and is the answer not in the manual?

ABB i-bus KNX AC/S 1.x.1 Series Specifications

General IconGeneral
BrandABB
Modeli-bus KNX AC/S 1.x.1 Series
CategoryController
LanguageEnglish

Related product manuals