EasyManuals Logo
Home>ABB>Controller>i-bus KNX AC/S 1.x.1 Series

ABB i-bus KNX AC/S 1.x.1 Series User Manual

ABB i-bus KNX AC/S 1.x.1 Series
488 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #63 background imageLoading...
Page #63 background image
ABB i-bus
®
KNX
Parameters
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 63
7.2.2.5 Clock parameter page
Clock synchronization source
Options:
NTP
KNX
BACnet
• NTP: The device clock is set using a time server in the IP network or the Internet. The device must be
able to communicate with the time server and access must not be blocked (e.g. by a firewall).
• KNX: The device clock is set via the KNX bus. The KNX time server must be connected to the related
device group objects.
• BACnet: The device clock is set via the BACnet bus. The device clock must be set via the BACnet
time synchronization function by the BACnet time server.
Selection of NTP option:
Dependent parameter(s):
NTP server
Information on the IP address or the NTP time server's domain.
Time zone
Selection of the time zone in which the device is located.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB i-bus KNX AC/S 1.x.1 Series and is the answer not in the manual?

ABB i-bus KNX AC/S 1.x.1 Series Specifications

General IconGeneral
BrandABB
Modeli-bus KNX AC/S 1.x.1 Series
CategoryController
LanguageEnglish

Related product manuals