ABB i-bus
®
KNX
Parameters
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 229
7.8 Room setpoint temperatures ASM
7.8.1 General
With this application-specific automation module (ASM), room setpoint temperatures for the various room
operating modes (Comfort, Standby, Economy and Building Protection) can be set centrally for several
rooms via the web user interface. The application controller outputs the room setpoint temperatures set on
the KNX bus, on the ASM output socket and on BACnet. If the values are linked to several controllers at
the same time, these values can apply to several rooms.
The operating modes for which the setpoint temperatures can be set via the web user interface can be
changed in the parameters for the module.
The module has a validation function so that invalid setpoint combinations cannot be set via the web user
interface. For information on validation, see Initial values and WebUI.