ABB i-bus
®
KNX
Parameters
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 59
7.2.2 DCA device settings
You can open the DCA device settings using the Settings button on the DCA menu bar. See
chapter 6.5.6,
Menu bar.
7.2.2.1 IP network parameter page
Setting for the DNS server address. This address is required so that the device can resolve domains and
therefore, for example, contact the NTP server for the time synchronization.
You will find the general IP settings for the device in chapter 6.3.1, Network Settings.
7.2.2.2 KNX parameter page
Rate of telegrams
Options:
Do not limit
1
2
3
5
10
20
This parameter defines how many KNX telegrams the device is allowed to send on the KNX bus per
second. If this value is exceeded, the device saves the telegrams and sends them the next time possible.
If the value of a group object not yet sent changes in the meantime, only the latest value is sent.
This parameter is also displayed in the device's ETS KNX parameter window and can be changed there.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB i-bus KNX AC/S 1.x.1 Series and is the answer not in the manual?

ABB i-bus KNX AC/S 1.x.1 Series Specifications

General IconGeneral
BrandABB
Modeli-bus KNX AC/S 1.x.1 Series
CategoryController
LanguageEnglish

Related product manuals