ABB i-bus
®
KNX
Parameters
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 445
7.17.3 Sockets
Overview of the ASM sockets for linking to other modules:
Input sockets
None
Output sockets
Object name Data type
State
DPT 20.102
The current value, based on the scheduler, is output for the linking to other modules.
Signal value:
1 = Comfort
2 = Standby
3 = Economy
4 = Building Protection
7.17.4 Group objects
Object function Name (can be changed separately) Data type Flags
Output: State
Operating mode Scheduler BACnet
1 byte
DPT 20.102
C, R, T
The current value, based on the scheduler, is output.
Telegram value: 1 = Comfort
2 = Standby
3 = Economy
4 = Building Protection