4-76 469 Motor Management Relay GE Power Management
4.12 S11 MONITORING 4 SETPOINT PROGRAMMING
4
4.12.4 PULSE OUTPUT
This feature configures one or more of the output relays as a pulsed output. When the programmed interval
has transpired the assigned relay will be activated for 1 second.
This feature should be programmed such that no more than one pulse per second will be required or
the pulsing will lag behind the interval activation.
y
PULSE OUTPUT
y
[ENTER] for more
POS kWh PULSE OUTPUT
RELAY: Off
Range: Off, Latched, Unlatched
POS kWh PULSE OUTPUT
INTERVAL: 1 kWh
Range: Breaker, Contactor
POS kvarh PULSE OUT
RELAY: Off
Range: Alarm, Alarm & Auxiliary2, Alarm & Aux2 & Aux3,
Alarm & Auxiliary3, Auxiliary2, Aux2 & Aux3, Auxiliary3
POS kvarh PULSE OUT
INTERVAL: 1 kvarh
Range: 10 to 1000 ms, step 10
NEG kvarh PULSE OUT
RELAY: Off
Range: Disabled, 52 Closed, 52 Open/Closed
Message seen only if Starter Type is Breaker
NEG kvarh PULSE OUT
INTERVAL: 1 kvarh
Range: On, Off
RUNNING TIME PULSE
RELAY: Off
Range: Disabled, 52 Closed, 52 Open/Closed
Message seen only if Starter Type is Breaker
RUNNING TIME PULSE
INTERVAL: 0 sec
Range: On, Off
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
NOTE