RFI lters / Mains lters
Basic informaon on RFI lters, mains lters and EMC: from ^ 246
EMC lters can be used both in the side structure and in the substructure.
Maximum motor cable lengths and FI operaon
Mains connecon 3-phase, 400 V/480 V, Light Duty
Inverter i550-C3.0/400-3 i550-C7.5/400-3 i550-C15/400-3 i550-C30/400-3
i550-C4.0/400-3 i550-C11/400-3 i550-C18/400-3 i550-C37/400-3
i550-C5.5/400-3 i550-C22/400-3 i550-C45/400-3
i550-C55/400-3
i550-C75/400-3
Without RFI lter
Without EMC cat-
egory
Thermal limitaon
Max. motor cable
length shielded
m 100 100 100 100
Max. motor cable
length unshielded
m 200 200 200 200
With integrated RFI lter
Category C1 Max. motor cable
length shielded
m - - - -
Category C2 m 20 20 20 20
Earth-leakage circuit
breaker
mA 300 300 300 300
RFI lter Low Leakage
Category C1 Max. motor cable
length shielded
m - - - -
Earth-leakage circuit
breaker
mA - - - -
RFI lter Short Distance
Category C1 Max. motor cable
length shielded
m 25 25 - -
Category C2 m 50 50 - -
Earth-leakage circuit
breaker
mA 30 30 - -
RFI lter Long Distance
Category C1 Max. motor cable
length shielded
m 50 50 - -
Category C2 m 100 100 - -
Earth-leakage circuit
breaker
mA 300 300 - -
Short Distance
Inverter RFI lter
Order code Dimensions (h x b x t) Weight
mm kg
i550-C3.0/400-3
I0FAE255F100S0000S 346 x 90 x 60 2.1i550-C4.0/400-3
i550-C5.5/400-3
i550-C7.5/400-3
I0FAE311F100S0000S 371 x 120 x 60 2.4
i550-C11/400-3
Technical data
3-phase mains connecon 480 V "Light Duty"
RFI lters / Mains lters
199