EtherNet/IP
EtherNET/IP is a common eldbus for the connecon of inverters to dierent control systems
in plants.
General informaon
Design Oponal
Integrated in standard I/O
DC supply of the control electronics
and oponal eldbus
internally via the inverter Mains-dependent
oponally:
External supply
Mains-independent
24 V DC
at X3/24E...GND
Terminal descripon EtherNet/IP EtherNet/IP
Connecon X266 X267
Connecon type RJ45
Max. cable cross-secon mm² - -
Max. cable cross-secon AWG - -
Stripping length mm - -
Stripping length inch - -
Tightening torque Nm - -
Tightening torque lb-in - -
Required tool -
Technical data
Communicaon prole EtherNet/IP
AC Drive
Bus terminang resistor not required
integrated bus terminang resistor No
Network topology
Without repeater Tree, star and line
With repeater -
Staon
Type Adapter (slave)
Max. number 254 Per subnetwork
Address Staon name
Max. cable length m - Not limited
The length between the nodes is decisive.
Max. cable length between two nodes m 100
Process data
Transmit PDOs 16 words max. 32 bits (4 bytes) as a coherent PDO
object
Receive PDOs 16 words
Cycle me ms > 4
Switching method Store-and-Forward
Cut-Through
Switch latency µs ~ 125 At maximum telegram length
Other data Addional TCP/IP channel
Communicaon me
Communicaon me depends on
Processing me in the inverter Time between the start of a request and
arrival of the response
Telegram runme (baud rate, telegram
length)
Nesng depth of the network
Bus load
Product extensions
Networks
EtherNet/IP
222