Firmware 03.00 - DMS EN 5.0 - 07/2009 L 131
8400 BaseLine D | Software Manual
Error management
Error messages of the operating system
7.5.2 Reset of error message
An error message with the response "Fault", "Trouble" or "Warning locked" must be
explicitly reset (acknowledged) after the cause of the error has been eliminated.
Error messages can be reset via
•the code C002/19
= "1"
• the »Engineer«
• the DCTRL input with C701/2
= "1" (terminal "X4/RFR": Low ---> High)
• Mains switching (switching off the mains and then on again)
Tip!
With an online connection to the controller, use the Diagnostics tab of the
»Engineer« and click Error message reset to reset a pending error message.