1-3
Installation 15088: J 10/22/99
Introduction
Capabilities and Capacities
The AM2020/AFP1010 is an Intelligent Analog Addressable Combination Fire Alarm/Security Control Panel
capable of supporting the following:
Intelligent Analog Addressable Fire Detectors
Photoelectric, ionization, and thermal (heat) detectors.
Intelligent Addressable Fire and Security Initiating Devices
Pull Stations and modules that monitor any conventional normally open contact type devices (4-wire smoke
detectors, heat detectors, pull stations, supervisory switches, water flow switches), 2-wire conventional smoke
detectors or any normally closed contact type device, such as a door contact that may be used in security
applications.
Intelligent Addressable Notification Devices and Addressable Control Relays
Modules that can supervise and switch power to notification appliances or serve as Form-C control relays.
Notification Appliance Power
Notification appliance power is provided by the main power supply. Additional notification appliance power may
be provided by optional power supplies listed for fire protective signaling.
Voice Evacuation Functions
Prerecorded or live voice alarm messages can be dispatched through an audio message generator. A fire
fighter's master telephone unit allows communication between the control panel and fire fighter's telephones
installed throughout the system.
Audio Amplifier Power
Audio power is provided by several sizes of audio amplifiers for use in voice alarm applications.
Peripherals
An AM2020/AFP1010 system can support remotely-mounted video display units, printers, and serial
annunciators.
AM2020 Maximum Intelligent Addressable Device Capacity (10 LIB-200/LIB-200A or five LIB-400 modules)
990 Intelligent photoelectric, ionization, and thermal (heat) detectors.
+ 990 Addressable pull stations, monitor modules, control modules and XP Transponder circuits.
= 1980 Addressable devices system wide.
AFP1010 Maximum Intelligent Addressable Device Capacity (four LIB-200/LIB-200A or two LIB-400
modules)
396 Intelligent photoelectric, ionization, and thermal (heat) detectors.
+ 396 Addressable pull stations, monitor modules, control modules and XP Transponder circuits.
= 792 Addressable devices system wide.
To the right are general terms and
their associated specific part numbers
as referenced in this manual:
Note: The term "loop" is used in a general way throughout this document and does not necessarily mean that the
circuit is a Class A configuration, unless a reference is made to Style 6, Style 7, Style D or Style Z circuit
performance.