Appendices 15088:J 10/22/99
A-3
APPENDIX A
CIRCUIT/DEVICE RATINGS
GENERAL
Appendix A outlines the various circuits and devices that can be employed with the AM2020/AFP1010.
SECTION A.1 DESIGN CONSIDERATIONS
Each of the various types of circuits within an AM2020/AFP1010 Fire Alarm Control System has a specific
type of wire that must be used in order to ensure proper operation. In addition, the wire gauge of a particular
circuit is contingent on the length of that circuit. To determine the specific wiring requirements for each circuit,
refer to Table A-1.
NOTES
• If the SLC Loop is to be run in conduit with Notification Appliance Circuits, the risk of encountering problems can be
greatly reduced by using the LIB-200A or LIB-400 or exclusively employing electronic sounders instead of more elec-
tronically noisy notification appliances such as electromechanical bells or horns.
• In order to comply with the Federal Communications Commission (FCC) regulations on electrical energy
radiation when using the LIB-200, any wire entering or exiting the AM2020/AFP1010 cabinet that is not in
conduit must be of the twisted-shielded type. For termination of the LIB-200 SLC Loop shield, refer to the
Installation section of the manual originally supplied with the LIB-200.
Table A-1 Wiring Selection Chart
Circuit
Type
Circuit Functions Wire Requirements
Distance
(feet/meters)
Typical Wire Type
LIB-200
SLC loop
Connects to Intelligent
Detectors and
Addressable Modules,
and to XP Transponders
Twisted-shielded pair, 12 to 18 AWG
(3.25 to 0.75 mm²). 40 ohms max
per length of Style 6 and 7 loops. 40
ohms per branch max for Style 4
loops.
10,000/3048
8,000/2438
4,875/1485.9
3,225/982.98
Belden 9583, West Penn 999, Belden B5020FL
(12 AWG/3.25 mm
2
)
Belden 9581, West Penn 995 (14 AWG/2.00 mm
2
)
Belden 9575, West Penn 991 (16 AWG/1.30 mm
2
)
Belden 9574, West Penn 975 (18 AWG/0.75 mm
2
)
LIB-200A or
LIB-400
SLC loop
Connects to Intelligent
Detectors and
Addressable Modules,
to XP Transponders,
and XP5 Transponders
Twisted unshielded pair, 12 to 18
AWG (3.25 to 0.75 mm²). 50 ohms
max per length of Style 6 and 7
loops. 50 ohms per branch max for
Style 4 loops
12,500/3810
9,500/2895.6
6,000/1828.8
3,700/1127.76
Belden 9582, West Penn 998 (12 AWG/3.25 mm
2
)
Belden 9580, West Penn 994 (14 AWG/2.00 mm
2
)
Belden 9572, West Penn 990 (16 AWG/1.30 mm
2
)
Belden 9571, West Penn 980 (18 AWG/0.75 mm
2
)
EIA-485
Connects to LCD-80,
AMG-1 and to
Annunciator Control
System Modules
Twisted-shielded pair with a
characteristic impedance of
approximately 120 ohms.
18 AWG (0.75 mm²) minimum.
6,000/1828.8
6,000/1828.8
6,000/1828.8
4,000/1219.2
Belden 9583, West Penn 999, Belden B5020FL
(12 AWG/3.25 mm
2
)
Belden 9581, West Penn 995 (14 AWG/2.00 mm
2
)
Belden 9575, West Penn 991 (16 AWG/1.30 mm
2
)
Belden 9574, West Penn 975 (18 AWG/0.75 mm
2
)
EIA-232
Connects to CRTs and
remote printers
Twisted-shielded pair.
18 AWG (0.75 mm²) minimum.
See EIA-232D
Standard
Belden 9583, West Penn 999 Belden B5020FL
(12 AWG/3.25 mm
2
)
Belden 9581, West Penn 995 (14 AWG/2.00 mm
2
)
Belden 9575, West Penn 991 (16 AWG/1.30 mm
2
)
Belden 9574, West Penn 975 (18 AWG/0.75 mm
2
)
MMX
XPM-8
Initiating Device Circuit
12 to 18 AWG(3.25 to 0.75 mm²).
Maximum loop wire resistance is 20
ohms (MMX-1, MMX-101) or 100
ohms (XPM-8).
5,000/1524
4,000/1219.2
2,438/743.1
1,613/491.64
Belden 9583, West Penn 999, Belden B5020FL
(12 AWG/3.25 mm
2
)
Belden 9581, West Penn 995 (14 AWG/2.00 mm
2
)
Belden 9575, West Penn 991 (16 AWG/1.30 mm
2
)
Belden 9574, West Penn 975 (18 AWG/0.75 mm
2
)
CMX
XPC-8
Notification Appliance
Circuit
12 to 18 AWG (3.25 to 0.75 mm²).
MPS-24A: At alarm current level, no
more than a 1.2 volt drop at the end
of the circuit.
Installer
Calculations
Required
Belden 9583, West Penn 999, Belden B5020FL
(12 AWG/3.25 mm
2
)
Belden 9581, West Penn 995 (14 AWG/2.00 mm
2
)
Belden 9575, West Penn 991 (16 AWG/1.30 mm
2
)
Belden 9574, West Penn 975 (18 AWG/0.75 mm
2
)
Power Runs
To CMXs, XPC-8s, and
XP5-Cs
12 to 18 AWG (3.25 to 0.75 mm²).
Size wire so that no more than 1.2
volt drop across wire run from supply
source to end of any branch.
Installer
Calculations
Required
Belden 9583, West Penn 999, Belden B5020FL
(12 AWG/3.25 mm
2
)
Belden 9581, West Penn 995 (14 AWG/2.00 mm
2
)
Belden 9575, West Penn 991 (16 AWG/1.30 mm
2
)
Belden 9574, West Penn 975 (18 AWG/0.75 mm
2
)
Power Runs To annunciators
12 to 18 AWG (3.25 to 0.75 mm²).
Size wire so that no more than 2.4
volts drop across wire run from
supply source to end of any branch.
Installer
Calculations
Required
Belden 9583, West Penn 999, Belden B5020FL
(12 AWG/3.25 mm
2
)
Belden 9581, West Penn 995 (14 AWG/2.00 mm
2
)
Belden 9575, West Penn 991 (16 AWG/1.30 mm
2
)
Belden 9574, West Penn 975 (18 AWG/0.75 mm
2
)