3-32
Programming 15088:J 10/22/99
Section 1.3.2 Control-By-Event D }X3X2X
2=CBE
Option 2 of the Partial Point Programming Menu allows the programmer to change the Control-By-Event (CBE)
for any detector, module or software zone. The panel maintains a CBE for each device and zone installed in
the system.
NOTE
A software zone is not a physical zone, but rather a software grouping in control panel memory.
When programming a particular device, the control panel prompts the programmer with:
ENTER@CONTROL-BY-EVENT@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@:
The following CRT screen display illustrates CBE programming for smoke detector number 23 on SLC Loop 2
to activate software zones 15 and 29.
PRESS@1=TYPID,2=CBE,3=LBL,4=OPTNS,5=AMAP,6=CCBE@@@@@@@@@@@@@@@@@@@@@@@@@@@@:@2
ENTER@LXX(D/M)YY,@ZXXX@OR@AXXPYY@FOR@PT.@CHANGE@(BCKSPC@TO@ABORT)@@@@@:@L2D23
ENTER@CONTROL-BY-EVENT@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@:
(Z15@Z29)
For a complete description of the types, parameters, limitations, and guidelines of CBE programming, see
Control-By-Event Programming
in Section Four.
Section 1.3.3 Label D }X3X3X
3=LBL
Option 3 of the Partial Point Programming Menu allows the programmer to change the 20-character custom label
associated with each detector, module, or software zone in the system. Acceptable characters for device or zone
labels are as follows:
Letters A through Z, digits 0 through 9, periods (.), dashes (-), and spaces.
The following CRT display illustrates renaming control module 21 on SLC Loop 1.
PRESS@1=TYPID,2=CBE,3=LBL,4=OPTNS,5=AMAP,6=CCBE@@@@@@@@@@@@@@@@@@@@@@@@@@@@:@3
ENTER@LXX(D/M)YY,@ZXXX@OR@AXXPYY@FOR@PT.@CHANGE@(BCKSPC@TO@ABORT)@@@@@:@L1M21
ENTER@20@CHARACTER@CUSTOM@LABEL@@@@@@@@@@@@@@@@@@@@@@@@@@@:@MAIN@LOBBY@BELLS@@@
Programming Tip:
Creative use of the custom label feature allows the programmer to be extremely specific in naming each SLC
device. For instance, for a group of addressable devices congregated in a particular area (such as a floor or a
section of a building), map each device to the same software zone and label the zone to serve as an additional 20
characters of information to the individual device labels. Assume Detector 3 initiates an alarm.
Only the first zone listed in the control-by-event (CBE) list of the initiating devices will display the 20-character
label, along with the label of the initiating devices itself when in alarm.
Note: Since Annunciator points do not have individual custom labels, Annunciator addresses are invalid entries
on this menu.
ALARM: SMOKE(PHOTO) GUEST KITCHENALARM: SMOKE(PHOTO) GUEST KITCHEN
ALARM: SMOKE(PHOTO) GUEST KITCHENALARM: SMOKE(PHOTO) GUEST KITCHEN
ALARM: SMOKE(PHOTO) GUEST KITCHEN
3RD FLOOR WEST WING 05:48P 03/01/97 103 3RD FLOOR WEST WING 05:48P 03/01/97 103
3RD FLOOR WEST WING 05:48P 03/01/97 103 3RD FLOOR WEST WING 05:48P 03/01/97 103
3RD FLOOR WEST WING 05:48P 03/01/97 103
Detectors 1
through 5
all mapped to
the
same Software
Zone
Software Zone
D1 D2 D3 D4 D5
Specific locationSpecific location
Specific locationSpecific location
Specific location
General locationGeneral location
General locationGeneral location
General location
The result is a 40-character label that characterizes a particular addressable device.
www.PDF-Zoo.com

Table of Contents

Other manuals for Notifier AM2020

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier AM2020 and is the answer not in the manual?

Notifier AM2020 Specifications

General IconGeneral
BrandNotifier
ModelAM2020
CategoryFire Alarms
LanguageEnglish

Related product manuals