EasyManuals Logo
Home>Notifier>Fire Alarms>AM2020

Notifier AM2020 User Manual

Notifier AM2020
268 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #195 background imageLoading...
Page #195 background image
Programming 15088:J 10/22/99
3-53
Group 2:
Output Modules
• These Software Type IDs cannot be programmed for Signal Silence.
• These Software Type IDs do not have any control-by-event programming.
• If the Software Type ID requires Form-C relay function, the two tabs on the CMX must be broken.
Otherwise, the tabs must not be broken.
Display Label
ALARMS PEND
DACT CONNECT
GN ALRM FORC
GN ALARM
GENERAL PEND
GN TRBL FORC
PAGE
POWER (CONV)
GN SUPR FORC
TELEPHONE
TRBLS PEND
TROUBLE FORC
TROUBLE
GN WAT FORC
GN WATER FLW
Type ID
APND
DACT
GAC
GAS
GPND
GTC
PAGE
PWRC
SSC
TELE
TPND
TRC
TRS
WFC
WFS
Type of Device
CMX Control Module, an XPC-8 circuit, or an XP5-C (in NAC mode) that will
activate upon receipt of an alarm condition, and remain in the ON state until all
alarms have been ACKNOWLEDGED.
CMX Control Module configured as a Form-C relay, an XPR-8 relay, or an XP5-C (in
relay mode) that will delay the reporting of AC power loss. Any other trouble
condition will be reported immediately. This module is used in conjunction with a
digital alarm communicator.
CMX Control Module configured as a Form-C relay,an XPR-8 relay, or an XP5-C
(in relay mode) to switch power to a Reverse Polarity Trip Device for NFPA 72
Remote Station Fire Alarm Systems applications (RPT-680 required).
This type
can also be used for general alarm activation.
CMX Control Module, an XPC-8 circuit, or an XP5-C (in NAC mode) config-
ured as a Municipal Box Transmitter for NFPA 72 Auxiliary Fire Alarm Systems
applications (MBT-1 required).
This Type ID can also be used for general alarm
activation.
CMX Control Module, an XPC-8 circuit, or an XP5-C (in NAC mode) that will
activate upon receipt of an alarm and/or trouble condition, and remain in the
ON state until all events have been ACKNOWLEDGED.
CMX Control Module configured as a Form-C relay, an XPR-8 relay, or an XP5-C
(in relay mode) activated under any System Trouble condition.
CMX Control Module, an XPC-8 circuit, or an XP5-C (in NAC mode) config-
ured for remote paging (RPJ-1 required).
CMX Control Module configured as a Form-C relay or an XP5-C (in relay mode)
used to momentarily interrupt power (during system reset) to conventional 4-wire
smoke detectors powered from a remote main power supply.
CMX Control Module configured as a Form-C relay, an XPR-8 relay, or an XP5-C
(in relay mode) activated under any Supervisory condition (includes sprinkler type).
CMX Control Module, an XPC-8 circuit, or an XP5-C (in NAC mode) config-
ured for telephone operation.
Note: The CMX and XP5-C will not provide a ring-
back signal when a call is placed.
CMX Control Module, an XPC-8 circuit, or an XP5-C (in NAC mode) that will
activate upon receipt of a trouble condition, and remain in the ON state until all
troubles have been ACKNOWLEDGED.
CMX Control Module configured as a Form-C relay, an XPR-8 relay, or an XP5-C
(in relay mode) that will activate upon receipt of a trouble condition(s) and remain
in the ON state until the trouble(s) clear(s).
CMX Control Module, an XPC-8 circuit, or an XP5-C (in NAC mode) that will
activate upon receipt of a trouble condition(s) and remain in the ON state until
the trouble(s) clear(s).
CMX Control Module configured as a Form-C relay, an XPR-8 relay, or an XP5-C
(in relay mode) activated under any Water Flow condition.
CMX Control Module, an XPC-8 circuit, or an XP5-C (in NAC module mode)
configured as a Notification Appliance Circuit, activated under any Water Flow
alarm condition.
www.PDF-Zoo.com

Table of Contents