3-62
Programming 15088:J 10/22/99
NOT
Operator: The NOT operator inverts the state of the operand
(activated to deactivated OR deactivated to activated).
Equation: NOT(Z2)
The control module will remain activated UNTIL
the operand comes into alarm.
IF Software Zone 2 is in alarm,
THEN this control module will be deactivated.
XZONE
Operator: For
Cross Zone
operation, the XZONE
counting operator may be used.
Equation: XZONE(Z23)
IF ANY combination of two or more initiating
devices (L1D1, L1D2, L1D3, L1D4)
that have been programmed (Control-By-Event)
to this software zone (Z23) come into alarm,
THEN this control module will be activated.
Z2
L1M1
CMX
L1D4
NOT(Z2)
(Z2)
L1D3L1D2
L1M3
CMX
L1D1 L1D4
Z23
(Z23)
(Z23)
(Z23) (Z23)
XZONE(Z23)