4-13
Security 15088:J 10/22/99
RKS-S Remote Keyswitch w/MM Module:
Address: LXXMYY (Installer Specified).
Type ID: NOA
Control-By-Event: (Zab*)
Custom Label: Arming Switch
Tracking: Yes
Annunciator: Yes
Annunciator Point: AXXP1
Contact Switch w/MM Module:
Address: LXXMYY (Installer Specified).
Type ID: SACM
Control-By-Event: (Zac*)
Custom Label: Entry/Exit Door
Tracking: Yes
Annunciator: Yes
Annunciator Point: AXXP3
Programming Key for Figure 1.3-6
Figure 1.3-6 Single Tenant Security System with Entry/Exit Delay
Key
Motion Detector
Contact Switch
Pull Station
Smoke Detector
MM Security Area Monitor
Group Interface
*
MM C M
Contact Switch with MM Module
RKS-S Remote Keyswitch with MM Module
* Group Interface must be physically
located in either the protected
premises or the Central Station
AM2020/AFP1010
Central Station
Area6.cdr
MM CM
To Signaling
Line Circuit
TENANT A
AREA 1
(Perimeter
and
Interior)
*
ACM-16AT or ACM-32A Remote Annunciator
To Central Station
(via EIA-485 circuit)
Sample Annunciator Display (ACM-16AT)
Entry/Exit Door
www.PDF-Zoo.com

Table of Contents

Other manuals for Notifier AM2020

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier AM2020 and is the answer not in the manual?

Notifier AM2020 Specifications

General IconGeneral
BrandNotifier
ModelAM2020
CategoryFire Alarms
LanguageEnglish

Related product manuals