4-17
Security 15088:J 10/22/99
MM Security Access Monitor
Provide a unique annunciator point for each Security Access Monitor installed.
Notification Appliance w/CM Module
When using an optional control module for Notification Appliances intended to indicate a security violation, the
control module intended for Tenant A may be programmed with the following Control-By-Event equation:
AND(Zab* SDEL(00.00.00 00.15.00 (Zaj*)))
and Tenant B may be programmed with the following Control-By-Event equation:
AND(Zbb* SDEL(00.00.00 00.15.00 (Zbj*)))
resulting in 15 minutes of Notification Appliance activation after a security violation.
Program Tenant A using zone numbers Zaa through Zaj as in Figure 1-6. Program Tenant B as in Figure 1-6, but substitute
Zba through Zbj for Zaa through Zaj respectively. *Zaa through Zaj are each unique installer-specified zone numbers. Zaa is the
lowest specified zone number (highest priority) and Zaj is the highest specified zone number (lowest priority).
Example:
Zaa Zab Zac Zad Zae Zaf Zag Zah Zai Zaj
Z5 Z12 Z22 Z180 Z188 Z199 Z200 Z210 Z211 Z212
Zba Zbb Zbc Zbd Zbe Zbf Zbg Zbh Zbi Zbj
Z6 Z7 Z21 Z100 Z102 Z108 Z187 Z191 Z193 Z215
ïð
Zone Programming Notes for Figure 1.3-9
ï ð
Forward Zones Reverse Zones
Zone Boundary greater than or equal to Z22 and less than Z100.
The following system requirements are illustrated in Figure 1.3-9. See Table 1.1-1 in the introduction to this
section for monitor and control module options.
• One AM2020/AFP1010 Control Panel
• Multiple Security Supervisory Circuits Reporting to Central Station as a Single Area
• Multiple Protected Premises, each with System Arm/Disarm Capability and Central Station Ringback Signal
• The minimum security equipment required is as follows:
— Multiple MM Monitor Modules per Protected Area
— One Group Interface per Grouped Area
— Contact Switch for Each Entry/Exit Door
— RKS-S Keyswitch
— MM Monitor Modules
— ACM-16AT or ACM-32A Remote Annunciator for Each Entry/Exit Door
— Security Devices
Figure 1.3-9 Multiple Tenant Security System with Entry/Exit Delay
Key
Motion Detector
Contact Switch
MM CM
MM C M
TENANT A
AREA 1
(Perimeter
and
Interior)
MM C M
TENANT B
AREA 1
(Perimeter
and
Interior)
Contact Switch w/MM
MM Security Area Monitor
AM2020/AFP1010
Central Station
RKS-S Remote Keyswitch w/MM
Pull Station
Smoke Detector
Group Interface
*
Shaded Area Indicates
Second Tenant
ACM-16AT or ACM-32A Remote Annunciator
* Group Interface
must be physically
located in either the
protected premises or
the Central Station
Area7.cdr
*
Signaling
Line
Circuit
*
www.PDF-Zoo.com

Table of Contents

Other manuals for Notifier AM2020

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier AM2020 and is the answer not in the manual?

Notifier AM2020 Specifications

General IconGeneral
BrandNotifier
ModelAM2020
CategoryFire Alarms
LanguageEnglish

Related product manuals