Installation 15088:J 10/22/99
Secondary Power
27.6 V DC, supervised and power-limited.
Fast charge = 2 amps, trickle charge = 20 mA.
Battery -
Battery +
Neutral Out Hot In
Neutral In Hot Out
+ -
+
-
Battery Fuse (10A, 3AG)
Power Harnesses (P2, P4)
Connect to Plug A on the top of the ICA-4/
ICA-4L (3 amps maximum, P2 and P4
combined) or any other module or board
requiring internal power.
Power Ribbon Connector
Connect to P2 on the CPU-2020 or CPU-2
Four-Wire Smoke Detector Power
24V DC ( 200 mV ripple), 1 amp maximum. Filtered and resettable.
Power-limited but must be supervised via a Power Supervision
Relay.
3 amps maximum non-fire alarm load.
6 amps maximum fire alarm load.
For additional ratings, refer to Appendix A.
Figure 3.3-1 Field Wiring the MPS-24A or MPS-24AE Power Supply
MPM-2 Voltmeter/Ammeter Connector
LED Indicators
Earth Ground Fault
Battery Fail
AC Power Fail
NiCad High Charge Rate
Cut R27 to disable
Earth Ground Fault
Detection.
JP5:
Cut to make
notification appliance
power on TB3
Terminals 3 and 4 a
resettable 2-amp
maximum circuit.
JP1:
When
employing a
CHG-120,
Remote Battery
Charger JP1
must be cut.
Notification Appliance/
Annunciator Power
Power-limited, filtered, non-resettable, 3 amps
(in alarm) maximum. JP5 may be cut to convert
this notification appliance power (TB3 Terminals
3 and 4) to a resettable, 2-amp maximum circuit.
This output can also be used to power ACS
series annunciators (do not cut JP5).
JP2: must be cut
otherwise a short on the
notification appliance
power circuit (Terminals
3 and 4) would register
incorrectly as a loss of
primary (AC) power.
Earth Ground
Connect to chassis via a
Grounding Cable Assembly.