1-67
Installation 15088: J 10/22/99
+ +
+ +
+ +
+ +
--
--
--
--
+ -
MMX-1
MMX-2
Heat Detector Pull Station
SLC Loop Channel A
Supervised and power-limited
24 VDC Two-wire Smoke Detectors
See third bulleted
note above.
Power-limited
Figure 4.6-4 illustrates an MMX-1 monitoring normally open contact fire alarm initiating devices that do not
require power and an MMX-2 monitoring powered two-wire smoke detectors. Refer to Figure 4.6-6 for circuits
using four-wire detectors.
NOTES
• For additional ratings, refer to Appendix A.
• For connection of the initiating devices, refer to the manufacturer's installation instructions packaged with each device.
• For MMX-2 mount the appropriate ELR across terminals 8 and 9.
• For more information, refer to the MMX-2 Installation Instructions.
Figure 4.6-4 NFPA Style D Initiating Device Circuit
24V DC Four-Wire Smoke Detector Power
Up to one amp for four-wire smoke detectors can be drawn from TB3 terminals 1(+) and 2(-). Power is removed
from these terminals during system reset. This 24V DC regulated source is power-limited but must be supervised
via an end-of-line Power Supervision Relay (refer to Figures 4.6-5 and 4.6-6).
UL-listed 24 VDC Filtered Regulated Power
Limited Power Supply for Fire Protective
Signaling
or
MPS-24A/E, TB3 Terminal 1 (+) and 2 (-)
APS-6R, TB2 Terminal 1 (+) and 2 (-)
Terminal 3 (+) and 4 (-)
LIB SLC Port A ( - )
LIB SLC Port A (+)