Programming 15088:J 10/22/99
3-57
Group 13:
Annunciator Output
Type ID
ACON
AFCM
Type ID
ATEL
Type ID
ASUP
Type ID
MTRB
Type ID
MPAG
Display Label
ANN CONTROL
ANN FORC MAN
Display Label
ANN TELEPHON
Display Label
ANN SUPRVSRY
Display Label
TRBL MONITOR
Display Label
MONITOR PAGE
Group 15:
Annunciator Supervisory
Group 16:
Trouble Module
Group 17:
Page Module
Group 14:
Annunciator Telephone
Type of Device
Annunciator Point that indicates the state of any CMX Control Module, XPC-8
circuit, XPR-8 relay, or XP5-C circuit mapped to it. This annunciator point can also
be used for manual control of relays, speaker and notification circuits.
Annunciator Point that is not deactivated upon system reset. Used for fan
control and similar applications only with an FRCM control
device.
Type of Device
Annunciator Point that indicates the state of any CMX Control Module or
XPC-8 or XP5-C circuit configured for telephone operation. This annuncia-
tor point can also control the state (connect/disconnect) of the circuit.
Type of Device
Annunciator Point that indicates the state of any SPSU or SUPR module
mapped to it.
Type of Device
MMX Monitor Module, an XPM-8 circuit, or an XP5-M circuit used to
monitor any trouble contacts external to the system. This module will be ac-
tivated by either an open or a short condition, and produces a POINT
TROUBLE message in the display. A Control-By-Event equation need
not be entered for this type since it only produces a trouble signal, not an
alarm.
Type of Device
MMX Monitor Module or an XPM-8 circuit or XP5-M circuit dedicated to a normally
open switch. Activation of a module with Software Type ID MPAG connects the
remotely located Fire Fighter's Telephone handset to the paging system. This Type
ID is used in conjunction with the PAGE Type ID (RPJ-1 required).
Note: This software type can be used to monitor power from an Uninterruptable Power Supply (UPS) under
NFPA 72 Proprietary Fire Alarm Systems applications or to monitor remote Main Power Supply in XP
Transponder systems.
www.PDF-Zoo.com

Table of Contents

Other manuals for Notifier AM2020

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier AM2020 and is the answer not in the manual?

Notifier AM2020 Specifications

General IconGeneral
BrandNotifier
ModelAM2020
CategoryFire Alarms
LanguageEnglish

Related product manuals