1-88
Installation 15088:J 10/22/99
Section 5.3 Remote Printers
The AM2020/AFP1010 can employ PRN Remote
Printers. This printer provides a hard-copy printout of
all status changes within the system and time-
stamps the printout with the current time-of-day and
date. The PRN provides 80 columns of data on
standard 9 inch by 11 inch tractor-feed paper.
Installation
Remote printers require 120 VAC, 50/60Hz primary
power. A secondary power source (battery backup) is
not provided; the use of a separate Uninterruptable
Power Supply (UPS) 50 watt minimum, UL listed for
Fire Protective Signaling is recommended. A UPS is
required for NFPA 72 Proprietary Protected Premises
Receiving Unit applications.
Connection between the control panel and PRN is
provided through an EIA-232 interface on the Serial
Interface Board. An installer provided cable must be
assembled for connection to the printer's EIA-232
port. Refer to Figure 5.3-2 for wiring instructions.
Using a special print feature, the PRN allows all
information programmed into the panel to be printed
out (including system configuration and addressable
device parameters).
NOTE
The PRN is factory programmed.
Printer Configuration
Refer to the documentation supplied with the PRN for
instructions on the printer’s menu controls. Set the
printer’s options as follows:
L/R ADJUST: 0
FONT: HS DRAFT
LPI: 6 CPI
ESC CHARACTER: ESC
BIDIRECTIONAL COPY: ON
CG-TAB: GRAPHIC
COUNTRY: E-USA ASCII
AUTO CR: OFF
LANGUAGE: ENGLISH
AUTO TEAR: 1S
COLOR OPTION: NOT INSTALLED
FORMLEN:
LINES: 6 LPI=60
STANDARD: EXECUTIVE 10.5"
CPI: 10 CPI
SKIP: 0.5"
EMULATE: EPSON
I/O:
BUFFER: 36K FOR PRN-4
40K FOR PRN-5
SERIAL:
BAUD: 2400
FORMAT: 7 BIT, EVEN, 1 STOP
PROTOCOL: XON/XOFF
CHARACTER SET: STANDARD
S1. ZERO: ON
AUTO LF: OFF
MENLOCK: ALL
PAPER:
BIN 1: 12/72"
BIN 2: 12/72"
SINGLE: 12/72"
PUSH TRA: 12/72"
PULL TRA: 12/72"
PAP ROLL: 12/72"
PAPOPT: NO
Twisted Pair
nc
Twisted Pair
50 feet (15.24 meters)
(typical)
Wiring distance limited
by cable capacitance.
See EIA-232E standard.
Plug this DB-25 connector into the
EIA-232 Port of the printer.
1 EIA-232 Reference
2 Transmit to Printer
3 EIA-232 Reference
4 Receive From Printer
SIB (Connector P3)
PRN
Remote
Printer
SIB-2048A
or
SIB-NET
Figure 5.3-1 Remote Printer to SIB Connections
NOTES
• Outputs are power limited but not supervised.
• Make connections with overall foil/braided-shield
twisted pair cable.
• Near Letter Quality (NLQ) mode cannot be used on
this printer.
www.PDF-Zoo.com

Table of Contents

Other manuals for Notifier AM2020

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier AM2020 and is the answer not in the manual?

Notifier AM2020 Specifications

General IconGeneral
BrandNotifier
ModelAM2020
CategoryFire Alarms
LanguageEnglish

Related product manuals