Programming 15088:J 10/22/99
3-47
Figure 2-2 Walk Test Option Flow Chart
6 = WALK
Select Walk Test
Submenu Option 1-6
1 = SEL
(select LIBs for Walk Test)
2 = UNP
(generates report for
unprogrammed devices)
3 = UNI
(generates report for
uninstalled devices)
4 = TEST
(generates report for tested
devices)
6 = EXIT
(Exits Walk Test Option)
Enter LIB # for Test
Report
Request/Abort
Test Report
Enter LIB # Included
in Test
Enter
Another LIB
for Test?
(Exit Alter Status Mode)
5 = UNTST
(generates report for untested
devices)
Yes
No
(Exit Alter Status Mode, see
notes under 1=SEL)
(Prints report, Exit Alter Status Mode)
1=SEL - Select C | X6X1X
This option allows the programmer to select which LIBs will participate in Walk Test. The following example selects
LIBs 1 and 3 for Walk Test:
PRESS@1=SEL,2=UNP,3=UNI,4=TEST,5=UNTST,6=EXIT@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@:@1
ENTER@LIB@NUMBER@TO@BE@INCLUDED@IN@WALK@TEST@(1@-@10)@@@@@@@@@@@@@@@@@@@@@:@1
DO@YOU@WANT@TO@ENABLE@MORE@LIBS@FOR@WALK@TEST?@(Y=YES,N=NO)@@@@@@@@@@@@@@@@@:@Y
ENTER@LIB@NUMBER@TO@BE@INCLUDED@IN@WALK@TEST@(1@-@10)@@@@@@@@@@@@@@@@@@@@@:@3
DO@YOU@WANT@TO@ENABLE@MORE@LIBS@FOR@WALK@TEST?@(Y=YES,N=NO)@@@@@@@@@@@@@@@@@:@N
NOTES
• Upon completion of the walk test LIB selection, a system trouble is generated to indicate the control
panel is operating under limited fire protection. Only the LIBs selected for walk test are affected.
• Each LIB collects information immediately after it is selected. The programmer should not generate a
walk test report until 20 seconds after LIB selection or the report will be missing data and should be
considered invalid. If this happens, abort the walk test and start again.
• If one or more LIBs have been selected for walk test, additional LIBs cannot be selected without exiting
walk test.
• For every intelligent addressable device activated during walk test, a walk test count message is sent
to the printer.
• Conventional devices attached to an addressable device with a Software Type ID of SCON (or
equivalent) can not be individually tested with walk test, because walk test does not perform a reset on
PWRC (or equivalent) devices.
Do not perform a System Reset during a Walk Test. System Reset does
not function properly while in Walk Test mode of operation and may result in unwanted activation of
various output modules. If a system reset occurs during a Walk Test, exit Walk Test mode and re-enter.
• Walk Test will automatically abort if no devices are tested for 15 minutes.
www.PDF-Zoo.com

Table of Contents

Other manuals for Notifier AM2020

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier AM2020 and is the answer not in the manual?

Notifier AM2020 Specifications

General IconGeneral
BrandNotifier
ModelAM2020
CategoryFire Alarms
LanguageEnglish

Related product manuals