1-27
Installation 15088: J 10/22/99
Section 2.7 Display Interface Connection
DIA-1010 and/or DIA-2020 provide access to the system CPU and the optional SIB, and an EIA-232
unsupervised printer interface (refer to Figure 2.7-1). When terminal supervision is not required and the terminal
(if present) has no keyboard, the DIA-1010 and/or DIA-2020 provide an EIA-485 interface which may be used to
connect an LCD-80 (in Terminal Mode).
Figure 2.7-1 Display Interface Assembly
Display Interface Assembly (DIA-1010/DIA-2020) viewed from the rear.
Display Interface
Board (DIB)
TB1
J3
J4
6
1
NOTE
The plug-in terminal block TB1 may
be removed to facilitate field wiring
the LCD-80 and remote printer
connections (see below).
TB1
DIB J3
DIB J4
EIA-232 to Notifier PRN
or
Keltron Printer #VS4095/5
Outputs are power limited, but not supervised nor opto-isolated.
Connections must be made with overall foil/braided-shield
twisted paired cable suitable for EIA-232 and EIA-485
applications. The printer must be installed in the same room as
the control panel. Terminate shield at cabinet entrance only.
Plug this DB-25 connector into the
EIA-232 Port of either the PRN printer or
the Keltron Printer Number VS4095/5.
EIA-232
Reference
Connect ribbon
cable 75226 from
DIB J3 to CPU P3
Connect ribbon
cable 71046 from
DIB J4 to SIB P4
Out (-)
Return (-)
Return (+)
Out (+)
TB1
EIA-485 to LCD-80
NOTE
If a supervised CRT or CRT with keyboard has been installed,
this interface cannot be used. The CCM-1 Communications
Converter Module must be employed to connect the LCD-80 in
terminal mode. For details, refer to the LCD-80 Liquid Crystal
Display Manual listed in the Related Document Chart in the
front of this manual.
Transmit to
Printer
All terminals are
power-limited
All terminals
are power-
limited
www.PDF-Zoo.com