EasyManuals Logo
Home>Notifier>Fire Alarms>AM2020

Notifier AM2020 User Manual

Notifier AM2020
268 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #37 background imageLoading...
Page #37 background image
1-27
Installation 15088: J 10/22/99
Section 2.7 Display Interface Connection
DIA-1010 and/or DIA-2020 provide access to the system CPU and the optional SIB, and an EIA-232
unsupervised printer interface (refer to Figure 2.7-1). When terminal supervision is not required and the terminal
(if present) has no keyboard, the DIA-1010 and/or DIA-2020 provide an EIA-485 interface which may be used to
connect an LCD-80 (in Terminal Mode).
Figure 2.7-1 Display Interface Assembly
Display Interface Assembly (DIA-1010/DIA-2020) viewed from the rear.
Display Interface
Board (DIB)
TB1
J3
J4
6
1
NOTE
The plug-in terminal block TB1 may
be removed to facilitate field wiring
the LCD-80 and remote printer
connections (see below).
TB1
DIB J3
DIB J4
EIA-232 to Notifier PRN
or
Keltron Printer #VS4095/5
Outputs are power limited, but not supervised nor opto-isolated.
Connections must be made with overall foil/braided-shield
twisted paired cable suitable for EIA-232 and EIA-485
applications. The printer must be installed in the same room as
the control panel. Terminate shield at cabinet entrance only.
Plug this DB-25 connector into the
EIA-232 Port of either the PRN printer or
the Keltron Printer Number VS4095/5.
EIA-232
Reference
Connect ribbon
cable 75226 from
DIB J3 to CPU P3
Connect ribbon
cable 71046 from
DIB J4 to SIB P4
Out (-)
Return (-)
Return (+)
Out (+)
TB1
EIA-485 to LCD-80
NOTE
If a supervised CRT or CRT with keyboard has been installed,
this interface cannot be used. The CCM-1 Communications
Converter Module must be employed to connect the LCD-80 in
terminal mode. For details, refer to the LCD-80 Liquid Crystal
Display Manual listed in the Related Document Chart in the
front of this manual.
Transmit to
Printer
All terminals are
power-limited
All terminals
are power-
limited
www.PDF-Zoo.com

Table of Contents

Other manuals for Notifier AM2020

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier AM2020 and is the answer not in the manual?

Notifier AM2020 Specifications

General IconGeneral
BrandNotifier
ModelAM2020
CategoryFire Alarms
LanguageEnglish

Related product manuals