4-25
Security 15088:J 10/22/99
Ç ÈÇ È
causes Zone Zah* to
activate if entry/exit
time is exceeded.
causes Zone
Zah* to activate
if entry/exit door
is left open.
8. Zone Active 1.5 Min. After Arming System
Zone: Zag*
Type ID: RZON
Control-By-Event: DEL(00.01.30 (Zab*))
Custom Label: Installer Specified.
Annunciator: No (Not required).
9. Zone Providing 30 Sec. Entry/Exit Delay (En-
try/Exit Door Only) When System Is Armed
Zone: Zah*
Type ID: RZON
Control-By-Event:
OR(AND(Zab* Zag* Zae*) AND(Zab* Zaf*))
Custom Label: Installer Specified.
Annunciator: No (Not required).
10. Zone Active for a Minimum of 30 Sec. if Entry/
Exit Delay Is Violated (Entry/Exit Door Only)
When System Is Armed
Zone: Zai*
Type ID: RZON
Control-By-Event:
AND(Zab* SDEL(00.00.00 00.00.30 (Zah*)))
Custom Label: Installer Specified.
Annunciator: No (Not Required).
11. Zone Active at Least 30 Sec. for Any Security
Breach While System Is Armed
Zone: Zaj*
Type ID: RZON
Control-By-Event: OR(Zad* Zah* Zai*)
Custom Label: Installer Specified.
Annunciator: No (Not required).
12. Zone which remains Active until Reset when
security violation occurs and the System is
Armed.
Zone: Zak*
Type ID: RZON
Control-By-Event: SDEL(00.00.00 (Zaj*))
Custom Label: Installer Specified.
Annunciator: Yes
Annunciator Point: ArrP2
13. Zone Active when Tamper Switch Is Active
Zone: Zal*
Type ID: RZON
Control-By-Event: ( )
Custom Label: Installer Specified.
Annunciator: Yes
Annunciator Point: ArrP5
ï ð
For-
ward
Zones
Reverse
Zones
ïð
Notification Appliance w/CM Control Module
When using an optional Control Module for Notification Appliances intended to indicate a security violation, this
CM may be programmed with the following Control-By-Event equation:
AND(Zab* SDEL(00.00.00 00.15.00 (Zaj*)))
resulting in 15 minutes of Notification Appliance activation after a security violation.
*Zaa through Zal are each unique installer-specified zone numbers. Zaa is the lowest specified zone number (high-
est priority) and Zal is the highest specified zone number (lowest priority).
Example:
Zaa Zab Zac Zad Zae Zaf Zag Zah Zai Zaj Zak Zal
Z5 Z12 Z22 Z180 Z188 Z199 Z200 Z210 Z211 Z212 Z216 Z218
Zone Boundary greater than or equal to Z22 and less than Z180.
Figure 1.3-10 Programming Key (continued):
www.PDF-Zoo.com

Table of Contents

Other manuals for Notifier AM2020

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier AM2020 and is the answer not in the manual?

Notifier AM2020 Specifications

General IconGeneral
BrandNotifier
ModelAM2020
CategoryFire Alarms
LanguageEnglish

Related product manuals