3-14
Programming 15088:J 10/22/99
Section 1.1.6 External Equipment   D
}X1X6X
6=EXTEQ
Option 6 from the Partial System Programming Menu allows the changing of any optional features associated
with the CRT Monitor or Printer(s).
Terminal Supervision - Electrical supervision of the CRT Monitor. Unless terminal supervi-
sion is selected, the CRT will not beep (i.e., no bell characters will be
sent) when unacknowledged troubles or unacknowledged alarms are
present.
Terminal Status Line - The bottom line of the CRT will display the number of unacknowl-
edged alarms and troubles, and the total number of alarms and
troubles in the system. The Terminal Status Line appears on the
CRT display only.
Auxiliary Printer Monitoring - The AM2020/AFP1010 will monitor the auxiliary printer's Ready/Busy
line for error conditions. Note: The P40 is a special internal 40-col-
umn printer. This option should not be enabled for external 80-col-
umn printers.
Control Module Reporting - Control module state changes will be printed out.
NONA/NOA Module Reporting - Module state changes for modules with the Software Type ID NONA
or NOA will be printed out. See
Software Type IDs
for further infor-
mation on all Software Type IDs.
LED LATCH - Enables 99-device LED latching. See restrictions under LED Latch-
ing.
Printer Error Continue - Data will be transmitted to the printer under
Printer Error
conditions
(
Paper Out
or
Printer Off Line
generates an error condition under
which data may be lost).
Enable for special applications only.
Bidirectional Copy - The CRT will process data received through its AUX port.
Enable for
special applications only (see the CCM-1 Product Installation Docu-
ment).
Printer Trouble Inhibit - The AM2020/AFP1010 monitors the primary printer's Rx line for error
conditions. This option inhibits the generation of a trouble message
for
Paper Out
or
Printer Off Line
.
Enable for special applications only
(see the VGAS Installation manual).
Printer Reports Redirected to CRT- System reports will be echoed to the CRT interface.
Enable for spe-
cial applications only (see the VGAS Installation Manual and the
NAM-232 For Use With AM2020/AFP1010 Manual, Document
50424).
The External Equipment Option flow chart is located in Figure 1-6.
www.PDF-Zoo.com

Table of Contents

Other manuals for Notifier AM2020

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier AM2020 and is the answer not in the manual?

Notifier AM2020 Specifications

General IconGeneral
BrandNotifier
ModelAM2020
CategoryFire Alarms
LanguageEnglish

Related product manuals