EasyManuals Logo
Home>Notifier>Fire Alarms>AM2020

Notifier AM2020 User Manual

Notifier AM2020
268 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #75 background imageLoading...
Page #75 background image
1-65
Installation 15088: J 10/22/99
Section 4.6 Monitor Modules
The MMX-101 Monitor Module (Figure 4.6-2)
The MMX-101 Monitor Module is an addressable module that is functionally and electrically identical to an MMX-1
Monitor Module (configured for NFPA Style B), but offered in a smaller package for mounting directly in the
electrical box of the contact-type device being monitored. Unlike the MMX-1, the MMX-101 does not have an
LED indicating polling or alarm condition.
The MMX-1, MMX-2 and MMX-101 Monitor Modules are addressable modules that monitor normally open contact,
shorting type and alarm initiating devices. The MMX-2 can also monitor conventional two-wire smoke detectors. The
MMX-1 and MMX-2 Initiating Device Circuits (IDC) can be wired as an NFPA Style B or Style D Initiating Device
Circuits; the MMX-101 Initiating Device Circuits (IDC) can be wired Style B only. There is no limit to the number of
contact-type devices installed on a monitor module circuit (See NFPA 72 for possible code imposed limits. See the
Device Compatibility document for the maximum number of 2-wire smoke detectors that can be connected to the
MMX-2.) Refer to Figures 4.6-3 and 4.6-4 for MMX-1/MMX-2 wiring diagrams.
The MMX-1 and MMX-2 Monitor Modules (Figure 4.6-1)
SLC Loop Connections
Connect the SLC Loop to MMX-1 or MMX-2 terminals 1(-) and 2 (+). The MMX occupies one module address on
the SLC Loop. Set the rotary switches on the MMX to the particular SLC address required (each MMX requires
a unique module address, 01-99).
NFPA Style B Initiating Device Circuit
Connect the alarm initiating devices to a single two-wire circuit. This circuit cannot be T-Tapped or branched in
any fashion, and must be terminated across the last device by a listed ELR. Connect the circuit to MMX-1/MMX-
2 terminals 6 (-) and 7 (+).
NFPA Style D Initiating Device Circuit
Connect the normally open contacts of the alarm initiating devices as shown in Figure 4.6-4. This circuit cannot
be T-Tapped or branched in any fashion. No external ELR is required for Style D wiring.
MMX-2 Operating Power
The MMX-2 requires connection of a Notifier 24V DC filtered and resettable power supply on Terminals 3(-) and
4(+). This power connection is supervised by the MMX-2. A maximum of 40 MMX-2 modules may be installed on
a LIB due to increased power consumption over the MMX-1. Only use 2-wire smoke detectors which are UL
compatibility listed. See the Notifier Device Compatibility Document 15378 for a listing of devices.
SLC Loop (-)
SLC Loop (+)
24V DC (-)
MMX-2 only
24V DC (+)
MMX-2 only
Style D (-)
Style D (+)
Style B (+)
Style B (-)
Figure 4.6-1 MMX-1 or MMX-2 Monitor Modules
Set the module address with these switches
IDC (-) IDC (+)
(Yellow) (Violet)
NFPA Style B Initiating Device Circuit
Terminate with an End-of-Line Resistor 47K, 1/2-watt (A2143-00)
SLC Loop (+) (-) SLC Loop
(Red) (Black)
NOTE
For additional ratings,
refer to Appendix A.
Figure 4.6-2 MMX-101 Monitor Module
www.PDF-Zoo.com

Table of Contents

Other manuals for Notifier AM2020

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier AM2020 and is the answer not in the manual?

Notifier AM2020 Specifications

General IconGeneral
BrandNotifier
ModelAM2020
CategoryFire Alarms
LanguageEnglish

Related product manuals