EasyManuals Logo
Home>Notifier>Fire Alarms>AM2020

Notifier AM2020 User Manual

Notifier AM2020
268 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #46 background imageLoading...
Page #46 background image
1-36
Installation 15088:J 10/22/99
Table 3.2-1 AM2020/AFP1010 System Current Draw Calculations (2 of 2)
C
ATEGORY
COLUMN
A
P
RIMARY
,
N
ON
-F
IRE
A
LARM
C
URRENT
(
AMPS
)
(MPS-24A
OR
MPS-24E
OUTPUT
CURRENT REQUIRED WHEN OPERATING FROM
PRIMARY POWER
COLUMN
B
P
RIMARY
,
F
IRE
A
LARM
C
URRENT
(
AMPS
)
COLUMN
C
S
ECONDARY
,
N
ON
-F
IRE
A
LARM
C
URRENT
(
AMPS
)
Q
TY
X
[
CURRENT DRAW
]= T
OTAL
Q
TY
X
[
CURRENT DRAW
]= T
OTAL
Q
TY
X
[
CURRENT DRAW
]= T
OTAL
XP5 Series Transponders
XP5-M
XP5-C Relay
XP5-C NAC/telephone
[ ]
[ ]
[ ]
x[0.001651]=
x[0.000840]=
x[0.001481]=
[ ]
[ ]
[ ]
x[0.003000]=
x[0.000840]=
x[0.001481]=
[ ]
[ ]
[ ]
x[0.001651]=
x[0.000840]=
x[0.001481]=
Miscellaneous
CCM-1
A77-716B
RA-400Z(when on)
NIB-96
MBT-1
UZC-256
UDACT
[ ]
[ ]
[ ]
[ ]
n/a
[ ]
[ ]
x[0.107]=
x[0.020]=
x[0.006]=
x[0.022]=
n/a
x[0.035]=
x[0.100]=
[ ]
[ ]
[ ]
[ ]
[ ]
[ ]
[ ]
x[0.107]=
x[0.020]=
x[0.006]=
x[0.022]=
x[0.017]=
x[0.090]=
x[0.100]=
[ ]
[ ]
[ ]
[ ]
n/a
[ ]
[ ]
x[0.107]=
x[0.020]=
x[0.006]=
x[0.022]=
n/a
x[0.035]=
x[0.100]=
Notification Appliances
1
NOT APPLICABLE
[ ]
[ ]
x[ ]=
x[ ]=
NOT APPLICABLE
Other devices drawing power from
MPS-24A terminals TB3-3 and TB3-4
[ ]
[ ]
x[ ]=
x[ ]=
[ ]
[ ]
x[ ]=
x[ ]=
[ ]
[ ]
x[ ]=
x[ ]=
S
UBTOTALS FROM THIS PAGE
P
RIMARY
,
NON
-
ALARM
SUBTOTAL
:
P
RIMARY
,
ALARM
SUBTOTAL
:
S
ECONDARY
,
NON-FIRE
ALARM SUBTOTOTAL
:
S
UBTOTALS FROM PREVIOUS PAGE
P
RIMARY
,
NON
-
ALARM
SUBTOTAL
:
P
RIMARY
,
ALARM
SUBTOTAL
:
S
ECONDARY
,
NON-FIRE
ALARM SUBTOTOTAL
:
S
UM SUBTOTALS FROM EACH PAGE FOR
TOTALS
P
RIMARY
,
NON
-
ALARM
TOTAL
:
CANNOT
EXCEED
3.0
A
P
RIMARY
,
ALARM
TOTAL
:
CANNOT
EXCEED
6.0
A
S
ECONDARY
,
NON-FIRE
ALARM TOTAL
:
PLACE THIS TOTAL
IN TABLE 3.2-3 TO
DETERMINE A.H.
REQUIREMENT
1
I
NCLUDE ONLY THOSE DEVICES TO BE POWERED BY THE MAIN POWER SUPPLY
,
NOT AN AUXILIARY SUPPLY SUCH AS THE
AVPS-24
OR
APS-6R.
S
EE MANUFACTURER
'
S INSTRUCTIONS FOR APPLICABLE POWER DRAWS
.
www.PDF-Zoo.com

Table of Contents

Other manuals for Notifier AM2020

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier AM2020 and is the answer not in the manual?

Notifier AM2020 Specifications

General IconGeneral
BrandNotifier
ModelAM2020
CategoryFire Alarms
LanguageEnglish

Related product manuals