Commissioning via the built-in BOP
5.6 Function commissioning
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
123
5.6.3.12 Running the converter in hibernation mode
Functionality
To achieve energy-saving operation, you can enable the converter to run in either frequency
hibernation (P2365 = 1) or PID hibernation (P2365 = 2).
● Frequency hibernation: When the demand frequency falls below the minimum frequency
(P1080), the OFF delay (P2366) is started. When the OFF delay expires, the converter is
ramped down to stop and enters the hibernation mode. The converter has to go through
the ON delay (P2367) before restarting.