Commissioning via the built-in BOP
5.7 Restoring to defaults
SINAMICS V20 Converter
138 Operating Instructions, 10/2019, A5E34559884-012
5.7 Restoring to defaults
Restoring to factory defaults
Parameter
Function
Setting
P0003
User access level
= 1 (standard user access level)
P0010
Commissioning parameter
= 30 (factory setting)
P0970 Factory reset = 21: parameter reset to factory defaults deleting user defaults if
stored
Restoring to user defaults
Parameter
Function
Setting
P0003
User access level
= 1 (standard user access level)
P0010
Commissioning parameter
= 30 (factory setting)
P0970 Factory reset = 1: parameter reset to user defaults if stored, else factory de-
faults
After setting the parameter P0970, the converter displays "8 8 8 8 8" and then the screen
shows "P0970". P0970 and P0010 are automatically reset to their original value 0.

Table of Contents

Other manuals for Siemens SINAMICS V20

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS V20 and is the answer not in the manual?

Siemens SINAMICS V20 Specifications

General IconGeneral
Power Range0.12 kW to 30 kW
Overload Capacity150% for 60 seconds
Protection ClassIP20
Storage Temperature Range-40°C to +70°C
AltitudeUp to 1000 m without derating
Input Voltage3AC 380 V to 480 V
Output Voltage0 V to Input Voltage
Control ModesV/f control
Ambient Temperature Range-10°C to +60°C
Relative Humidity5% to 95%, non-condensing
Communication InterfacesModbus RTU
Braking ResistorOptional external

Related product manuals