EasyManuals Logo
Home>Siemens>Relays>siprotec 7SD5

Siemens siprotec 7SD5 User Manual

Siemens siprotec 7SD5
698 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #256 background imageLoading...
Page #256 background image
2 Functions
256
7SD5 Manual
C53000-G1176-C169-1
2.10.2.2 Setting Notes
Echo Enable In applications with a transmission channel used by both the distance and the earth
fault protection spurious trippings may occur, if distance protection and earth fault pro-
tection create an echo independently from each other. In this case parameter
Echo:1channel (address 2509) has to be set to YES. The default setting is NO.
Phase Selection Phase selection is accomplished via undervoltage detection. For this purpose no ab-
solute voltage threshold in volts is parameterized, but a factor (address 2510 Uphe<
Factor) which is multiplied with the measured phase-phase voltage, and yields the
voltage threshold. This method accounts for operational deviations from the nominal
voltage in the undervoltage threshold and adjusts them to the prevailing conditions.
Since a sound positive phase-to-phase voltage is not available in the event of a fault,
the undervoltage threshold is delayed. Thus changes in the positive phase--to-phase
voltage affect the threshold only slowly. The time constant can be set at address 2511
Time const. Ï„. The undervoltage is determined for all 3 phases.
If the measured phase-to-phase voltage falls below the threshold (address 1131
PoleOpenVoltage), undervoltage is no longer detected in this phase.
Figure 2-114 Undervoltage detection for U
L1–E
Non-delayed
Tripping
A non-delayed TRIP command is issued if a receive signal „>WI reception“ is
present and an undervoltage condition is detected simultaneously. If another protec-
tion function capable to detect faults has picked up in the relay, the corresponding
phases in the weak-infeed function are blocked. The receive signal is prolonged at
address 2512 Rec. Ext., so that a trip command is still possible in the event of a
quick dropout of the transmitting line end.
To avoid a faulty pick up of the weak infeed function following tripping of the line and
reset of the fault detection, the function cannot pick up any more once an inverse-time
overcurrent fault detection in the affected phase was present.
If a receive signal applies and no undervoltage is detected, but the zero sequence
current threshold 3I0> Threshold is exceeded (address 2514), a fault on the line
can be assumed. If this state (receive signal, no undervoltage and zero sequence cur-
rent) applies for longer than 500 ms, 3-pole tripping is initiated. The time delay for the
signal „3I0> exceeded“ is set at address 2513 T 3I0> Ext.. If the zero sequence
current exceeds the threshold 3I0> Threshold for longer than the set time T 3I0>
alarm (address 2520), the annunciation „3I0 detected“ is issued.
The non-delayed stage operates only if binary input „>WI rec. OK“ reports the
proper functioning of the transmission channel.
www . ElectricalPartManuals . com

Table of Contents

Other manuals for Siemens siprotec 7SD5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens siprotec 7SD5 and is the answer not in the manual?

Siemens siprotec 7SD5 Specifications

General IconGeneral
BrandSiemens
Modelsiprotec 7SD5
CategoryRelays
LanguageEnglish

Related product manuals