2 Functions
356
7SD5 Manual
C53000-G1176-C169-1
If double-ended fault locating is not desired, set address 3807 two ended = OFF. The
default setting is ON.
If the fault location is required to be output as BCD-code, set the maximum time period
the data should be available at the outputs using address 3811 Tmax OUTPUT BCD.
If a new fault occurs, the data are terminated immediately even when it occurs before
this time has expired. Allocate the corresponding output relays as stored if a longer
time period is desired for the output. Once a fault occurred the data will be latched until
the memory is reset or a new fault is registered.
2.19.3 Settings
2.19.4 Information List
Addr. Parameter Setting Options Default Setting Comments
3802 START Pickup
TRIP
Pickup Start fault locator with
3805 Paral.Line Comp NO
YES
YES Mutual coupling parall.line com-
pensation
3806 Load Compensat. NO
YES
NO Load Compensation
3807 two ended ON
OFF
ON two ended faulr location
3811 Tmax OUTPUT BCD 0.10 .. 180.00 sec 0.30 sec Maximum output time via BCD
No. Information Type of In-
formation
Comments
1111 FL active OUT Fault locator active
1113 quality= VI Quality of the fault location
1114 Rpri = VI Flt Locator: primary RESISTANCE
1115 Xpri = VI Flt Locator: primary REACTANCE
1117 Rsec = VI Flt Locator: secondary RESISTANCE
1118 Xsec = VI Flt Locator: secondary REACTANCE
1119 dist = VI Flt Locator: Distance to fault
1120 d[%] = VI Flt Locator: Distance [%] to fault
1122 dist = VI Flt Locator: Distance to fault
1123 FL Loop L1E OUT_Ev Fault Locator Loop L1E
1124 FL Loop L2E OUT_Ev Fault Locator Loop L2E
1125 FL Loop L3E OUT_Ev Fault Locator Loop L3E
1126 FL Loop L1L2 OUT_Ev Fault Locator Loop L1L2
1127 FL Loop L2L3 OUT_Ev Fault Locator Loop L2L3
1128 FL Loop L3L1 OUT_Ev Fault Locator Loop L3L1
1131 RFpri= VI Flt Locator: primary FAULT RESISTANCE
1132 Flt.Loc.invalid OUT Fault location invalid
1133 Flt.Loc.ErrorK0 OUT Fault locator setting error K0,angle(K0)
1134 two ended FO OUT_Ev Two ended fault location
1135 Rpri single. = VI R (primary, single ended)
www . ElectricalPartManuals . com

Table of Contents

Other manuals for Siemens siprotec 7SD5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens siprotec 7SD5 and is the answer not in the manual?

Siemens siprotec 7SD5 Specifications

General IconGeneral
BrandSiemens
Modelsiprotec 7SD5
CategoryRelays
LanguageEnglish

Related product manuals