2 Functions
416
7SD5 Manual
C53000-G1176-C169-1
2.24.1.3 Settings
2.24.2 Processing of Messages
After the occurrence of a system fault, data regarding the response of the protective
relay and the measured quantities should be saved for future analysis. For this reason
message processing is done in three ways:
2.24.2.1 Functional Description
Displays and
Binary Outputs
( o u t p u t r e l a y s )
Important events and statuses are displayed using front panel LEDs. The device fur-
thermore has output relays for remote indication. Most indications and displays can be
configured differently from the delivery default settings (for information on the delivery
default setting see Appendix). The SIPROTEC
®
4 System Description gives a detailed
description of the configuration procedure.
The output relays and the LEDs may be operated in a latched or unlatched mode
(each may be individually set).
Addr. Parameter Setting Options Default Setting Comments
4401 IP-A (A.x.x.x) 0 .. 255 141 IP-address ***.xxx.xxx.xxx(Posi-
tion 1-3)
4402 IP-B (x.B.x.x) 0 .. 255 142 IP-address xxx.***.xxx.xxx(Posi-
tion 4-6)
4403 IP-C (x.x.C.x) 0 .. 255 255 IP-address xxx.xxx.***.xxx(Posi-
tion 7-9)
4404 IP-D (x.x.x.D) 0 .. 255 150 IP-address xxx.xxx.xxx.***(Pos.
10-12)
4405 NUM LOCK YES
NO
YES Num Lock
4406 LCP/NCP NO
YES
YES Front interface supports
LCP/NCP mode
4411 IP-A (A.x.x.x) 0 .. 255 141 IP-address ***.xxx.xxx.xxx(Posi-
tion 1-3)
4412 IP-B (x.B.x.x) 0 .. 255 142 IP-address xxx.***.xxx.xxx(Posi-
tion 4-6)
4413 IP-C (x.x.C.x) 0 .. 255 255 IP-address xxx.xxx.***.xxx(Posi-
tion 7-9)
4414 IP-D (x.x.x.D) 0 .. 255 160 IP-address xxx.xxx.xxx.***(Pos.
10-12)
4415 NUM LOCK YES
NO
YES Num Lock
4416 LCP/NCP NO
YES
YES Service interface supports
LCP/NCP mode