4 Technical Data
574
7SD5 Manual
C53000-G1176-C169-1
4.24 Additional Functions
Measured Values
Operational measured values for currents I
L1
; I
L2
; I
L3
; 3I
0
; I
1
; I
2
; I
Y
; I
P;
I
EE
in A primary and secondary and in % I
N
Tolerance 0.5 % of measured value or 0.5 % of I
N
Phase angles of currents Ï•(I
L1
-I
L2
); Ï•(I
L2
-I
L3
); Ï•(I
L3
-I
L1
) in °
To le r a nc e 1° at nominal current
Operational measured values for voltages U
L1-E
, U
L2-E
, U
L3-E
; 3U
0
; U
0
; U
1
; U
2
; U
1Ko
in kV primary, in V secondary or in % U
N
/√3
Tolerance 0,5 % of measured value or 0,5 % of U
N
Operational measured values for voltages U
EN
; U
X
in V secondary
Tolerance 0.5 % of measured value, or 0.5 % of U
N
Operational measured values for voltages U
L1-L2
, U
L2-L3
, U
L3-L1
in kV primary, in V secondary or in % U
N
Tolerance 0.5 % of measured value or 0.5 % of U
N
Phase angle of voltages Ï•(U
L1
-U
L2
); Ï•(U
L2
-U
L3
); Ï•(U
L3
-U
L1
) in °
To le r a nc e 1 ° at nominal voltage
Phase angle for voltages and currents Ï•(U
L1
-I
L1
); Ï•(U
L2
-I
L2
); Ï•(U
L3
-I
L3
) in °
To le r a nc e 1° at nominal voltage and nominal current
Operational measured values of impedances R
L1-L2
, R
L2-L3
, R
L3-L1
, R
L1-E
, R
L2-E
, R
L3-E
,
X
L1-L2
, X
L2-L3
, X
L3-L1
, X
L1-E
, X
L2-E
, X
L3-E
in Ω primary and secondary
Operational measured values for power S; P; Q (apparent, active and reactive power)
in MVA; MW; Mvar primary and % S
N
(operational nominal power) = √3 · U
N
· I
N
Tolerance for S
Tolerance for P
Tolerance for Q
1% of S
N
at I/I
N
and U/U
N
in range 50 to 120 %
1% of S
N
at I/I
N
and U/U
N
in the range from 50 to 120 % and
ABS(cos ϕ) in the range ≥ 0,7
1% of S
N
at I/I
N
and U/U
N
in the range from 50 to 120 % and
ABS(cos ϕ) in the range ≤ 0,7
Operating measured value for power factor cos Ï•
To le r a nc e 0 .0 2
Counter values for energy W
p
+, W
q
+; W
p
-; W
q
- (active and reactive energy)
in kWh (MWh or GWh) and
in kVARh (MVARh or GVARh)
Tolerance at nominal frequency 5 % for I > 0.5 I
N
, U > 0.5 U
N
and | cosϕ | ≥ 0.707
Operational measured values for frequency f in Hz and % f
N
Range 10 Hz to 75 Hz
Tolerance 20 mHz in range f
N
± 10 % at nominal values
Measured values of the differential protection I
DIFFL1
; I
DIFFL2
; I
DIFFL3
;
I
RESTL1
; I
RESTL2
; I
RESTL3
;
I
CL1
; I
CL2
; I
CL3
;
I
DIFF3I0
in % I
NOperation
Thermal measured values ΘL1/Θ
TRIP
; Θ
L2
/Θ
TRIP
; Θ
L3
/Θ
TRIP
; Θ/Θ
TRIP
related to tripping temperature rise
Operational measured values of synchro check U
line
; U
sync
; U
diff
in kV primary
f
line
, f
sync
, f
diff
in Hz;
Ï•
diff
in°