2.2 Protection Data Interfaces and Protection Data Topology
83
7SD5 Manual
C53000-G1176-C169-1
2.2.2.2 Settings
Addresses which have an appended "A" can only be changed with DIGSI, under Ad-
ditional Settings.
Addr. Parameter Setting Options Default Setting Comments
4501 STATE PROT I 1 ON
OFF
ON State of protection interface 1
4502 CONNEC. 1 OVER F.optic direct
Com conv 64 kB
Com conv 128 kB
Com conv 512 kB
F.optic direct Connection 1 over
4505A PROT 1 T-DELAY 0.1 .. 30.0 ms 30.0 ms Prot 1: Maximal permissible delay
time
4506A PROT 1 UNSYM. 0.000 .. 3.000 ms 0.100 ms Prot 1: Diff. between send and
receive delay time
4509 T-DATA DISTURB 0.05 .. 2.00 sec 0.10 sec Time delay for data disturbance
alarm
4510 T-DATAFAIL 0.0 .. 60.0 sec 6.0 sec Time del for transmission failure
alarm
4511 PI1 SYNCMODE TEL and GPS
TEL or GPS
GPS SYNC OFF
TEL and GPS PI1 Synchronizationmode
4512 Td ResetRemote 0.00 .. 300.00 sec; ∞ 0.00 sec Remote signal RESET DELAY for
comm.fail
4513A PROT1 max ERROR 0.5 .. 20.0 % 1.0 % Prot 1: Maximal permissible error
rate
4515A PI1 BLOCK UNSYM YES
NO
YES Prot.1: Block. due to unsym. delay
time
4601 STATE PROT I 2 ON
OFF
ON State of protection interface 2
4602 CONNEC. 2 OVER F.optic direct
Com conv 64 kB
Com conv 128 kB
Com conv 512 kB
F.optic direct Connection 2 over
4605A PROT 2 T-DELAY 0.1 .. 30.0 ms 30.0 ms Prot 2: Maximal permissible delay
time
4606A PROT 2 UNSYM. 0.000 .. 3.000 ms 0.100 ms Prot 2: Diff. in send and receive
time
4611 PI2 SYNCMODE TEL and GPS
TEL or GPS
GPS SYNC OFF
TEL and GPS PI2 Synchronizationmode
4613A PROT2 max ERROR 0.5 .. 20.0 % 1.0 % Prot 1: Maximal permissible error
rate
4615A PI2 BLOCK UNSYM YES
NO
YES Prot.2: Block. due to unsym. delay
time
4801 GPS-SYNC. ON
OFF
OFF GPS synchronization
4803A TD GPS FAILD 0.5 .. 60.0 sec 2.1 sec Delay time for local GPS-pulse
loss
www . ElectricalPartManuals . com

Table of Contents

Other manuals for Siemens siprotec 7SD5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens siprotec 7SD5 and is the answer not in the manual?

Siemens siprotec 7SD5 Specifications

General IconGeneral
BrandSiemens
Modelsiprotec 7SD5
CategoryRelays
LanguageEnglish

Related product manuals