EasyManuals Logo
Home>Siemens>Relays>siprotec 7SD5

Siemens siprotec 7SD5 User Manual

Siemens siprotec 7SD5
698 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #280 background imageLoading...
Page #280 background image
2 Functions
280
7SD5 Manual
C53000-G1176-C169-1
Add (address 2656 for earth currents) are in addition to the time delays resulting from
the set curves.
The parameter I(3I0)p Tele/BI (address 2670) defines whether the time delays
Time Dial TD Ip (address 2643), including the additional delay T Ip Add (ad-
dress 2646), and TimeDial TD3I0p (address 2653), including the additional delay
T 3I0p Add (address 2656), can be bypassed by the binary input „>O/C
InstTRIP“ (No. 7110). The binary input (if allocated) is applied to all stages of the
time-overcurrent protection. With I(3I0)p Tele/BI = YES you define that the IP
stages trip without delay after pickup if the binary input was activated. For I(3I0)p
Tele/BI = NO the set delays are always active.
Instantaneous tripping by the operational auto-reclosure function should only be
chosen if the overcurrent protection is set to emergency function
. Since the fast main
protection function - differential protection and/or distance protection - guarantees a
fast and selective tripping with or without auto-reclosure, the overcurrent protection as
a back-up protection
may not perform a non-selective trip, even before auto-reclosure.
If the IP stage, when switching the line on to a fault, is to trip without delay or with a
short delay, SOTF Time DELAY (address 2680, see above under margin heading
„General“), the parameter I(3I0)p SOTF (address 2671) is set to YES. We recom-
mend, however, not to choose the sensitive setting for the switch on to a fault function
as energizing of the line on to a fault should cause a large fault current. It is important
to avoid that the selected stage picks up due to transients during line energization.
Additional Stage
I
ph
>>>
The I-STUB stage can be used as an additional definite time overcurrent stage, since
it works independently of the other stages. In this case, the enable input „>I-STUB
ENABLE“ (No 7131) must be activated permanently (via a binary input or CFC).
Since the I-STUB stage has an additional enable input, it is also suitable e.g. as an
emergency stage if the remaining stages are used as backup stages. The release
input „>I-STUB ENABLE“ (No. 7131) can be assigned the output signal „Emer.
mode“ (No. 2054) (either via binary outputs and inputs or via the user-definable logic
CFC functions).
The considerations for the use of the I-STUB stage as an emergency function are the
same as for the I> stages. The setting value Iph> STUB (address 2630) must here
too be higher than the maximum operational current to be expected, in order to avoid
pickup without fault. The delay T Iph STUB (address 2631), however, can be shorter
than defined in the time grading schedule, since this stage works only in emergency
operation, i.e. in case of a communication failure of the differential protection or a local
measurement voltage failure of the distance protection. Normally, one grading time
above the base time of the differential protection is sufficient.
The residual current stage 3I0> STUB (address 2632) should correspondingly pick
up on the smallest residual current to be expected during an earth fault and the delay
T 3I0 STUB (address 2633) should exceed the base time of the differential protec-
tion by one grading time. If only the phase currents are to be monitored, set the pickup
value of the residual current stage to ∞.
The I-STUB stage can also be accelerated by the enable signal „>O/C InstTRIP“
(No 7110), e.g. before an auto-reclosure. This is defined with parameter I-STUB
Telep/BI (address 2634). Set it to YES if the ISTUB stage is to trip without delay as
long as the binary input „>O/C InstTRIP“ is activated or the internal auto-reclosure
function is ready to operate. Instantaneous tripping by the operational auto-reclosure
should only be chosen if the I-STUB stage is set as an emergency function. If the main
protection function - differential and/or distance protection - are out of operation, this
emergency stage guarantees instantaneous tripping before auto-reclosure.
www . ElectricalPartManuals . com

Table of Contents

Other manuals for Siemens siprotec 7SD5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens siprotec 7SD5 and is the answer not in the manual?

Siemens siprotec 7SD5 Specifications

General IconGeneral
BrandSiemens
Modelsiprotec 7SD5
CategoryRelays
LanguageEnglish

Related product manuals