6.8 First setup of digital thermostats
Select thermostat control mode
If an external sensor is connected to the thermostat,
a control mode must be selected to accommodate the
extra functionality of the sensor.
NOTE!
If no button is pressed for about 8 seconds,
while in a submenu, the current values will be
saved and the software exits to the settings
menu. About about 60 seconds later, it exits
to run mode.
1. Press and hold the OK button until the settings
icon and menu numbers is displayed in the top right
corner of the display (about 3 seconds).
2. Use buttons - or + to change the numbers to 04
and press OK.
3. Current control mode is displayed (RT, RFT, RS or
RO).
4. Use buttons - or + to change control mode (see list
below) and press OK.
RT = Room temperature
RFT = Room temperature with external floor sensor
RS = Remote sensor
RO = Room temperature with remote outdoor
sensor
5. Press and hold the OK button for about 3 seconds
to exit the settings menu.
Temperature setpoint
The thermostats are delivered with a default setpoint of
21 °C.
The illustration below shows how to adjust the
thermostat temperature setpoint.
To adjust the thermostat temperature setpoint of the
current control mode:
1. Press the - or + button once.
The screen shows the current setpoint flashing.
T-166
T-167
T-168
2. Press the - or + button repeatedly to adjust the
setpoint temperature. It will change with increments
of 0.5.
When the new setpoint is set, the screen returns to
run mode after a few seconds, showing the room
temperature.
6.9 Register thermostats in controller
Registration at first startup
When starting the controller for the first time, it
automatically enters run mode, which is the standard
mode of operation. Go to step 1.
Registration if in run mode
Run mode is the standard mode of the controller when
the system is running according to set parameters. Go
to step 1.
Registration if in forced mode
Exit to run mode, see section 10.4 Run mode > Exit to
run mode, then go to step 1.