14.6 Main menu
The main menu is the top most menu and it uses icons
for navigation. Press an icon to enter a submenu to
change specific settings.
Menu tree
Main menu
System settings
General ECO setback
Valve/pump exercise
Supply diagnostic
Autobalance
Room check
Room bypass
SD card
Ceiling cooling settings
Holiday
Heating/Cooling
Cooling offset*
Operating mode*
Integration
Controller relay
General purpose input (GPI)
Relay output module
Heat pump integration
Trends
Alarms
Preferences
Language
Display
Regional settings
RF Link
Date & Time
Factory reset
System info
* Only visible if cooling is available in Heating/Cooling menu
14.7 System settings
In this menu, system specific settings can be changed.
General ECO setback
Default: 4.0 ˚C
Setting range: 0.0 – 11.0 ˚C, 0.5 ˚C increments
Set a general ECO setback value that will be used
to change the room setpoint temperature for all
thermostats when in ECO mode. It will lower the
setpoint in heating mode and raise the setpoint in
cooling mode.
NOTE!
Changing this value will reset any individual
room setback values already set and the new
value will be transmitted to the thermostats.
Valve/pump exercise
Default: Valve and pump
Setting range: Inactive, Valve only, Valve and pump
Set exercise mode once a week during periods of low
activity for the valves and/or pumps to avoid them
getting stuck.
If activated, a day and time can be set.
Supply diagnostic
Default: Inactive
Setting range: Active, Inactive
Activate a function checking whether the supply
temperatures are too high or too low. The result is
displayed after roughly 24 hours. If needed, information
on how to optimise the system is also displayed.
Autobalance
Default: Active
Setting range: Active, Inactive
Activate the autobalance function.
See section 3.5 Functions > Autobalance for more
information.