16.4 Controller alarms/problems
An alarm is sent when more than 1 hour have elapsed since the controller received the last radio signal from the thermostat.
The table below lists problems that can occur in the controller.
Indication Probable cause Solutions
The power LED and channel LED on
the controller flashes
The antenna is out of position or a wire is
disconnected
Install the antenna in a correct position with the cable
correctly connected
Alarm in the interface
The battery icon
is displayed in
room information on the interface or
thermostat
The batteries in the thermostat are discharged Replace the batteries
When the error is resolved, the thermostat screen displays
the room temperature and the battery icon disappears
Radio alarm in interface
The radio icon
is displayed in room
information on the thermostat
The power LED and thermostat LEDs
in the controller for the connected
channels flash
The thermostat is out of radio range Reduce the distance between the thermostat and controller
or change location of the thermostat in the room
16.5 Contact the installer
For installer contact information, see the installation
report in the end of this document. Prepare the
following information before contacting an installer:
Installation report
Drawings of the underfloor heating system (if
available)
List of all alarms, including time and date
16.6 Installer instructions
To determine if a problem is caused by the supply
system or the control system, loosen the actuators
from the manifold for the room concerned, wait a few
minutes and check if the flow pipe of the underfloor
heating loop becomes warm.
If the pipe does not become warm, the problem is in the
heating system. If the loop becomes warm, the cause
could be the room control system.
A supply system defect can be indicated by no warm
water in the manifold. Check the boiler and circulation
pump.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
89
UPONOR SMATRIX WAVE/WAVE PLUS
· INSTALLATION AND OPERATION MANUAL

Table of Contents

Other manuals for Uponor Smatrix Wave PLUS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Uponor Smatrix Wave PLUS and is the answer not in the manual?

Uponor Smatrix Wave PLUS Specifications

General IconGeneral
BrandUponor
ModelSmatrix Wave PLUS
CategoryFloor Heating Systems
LanguageEnglish

Related product manuals