Chapter 10 - Functions
10:8 Kick Start
Path in menu:
Menu/SETTINGS/Functional Settings/
Start/Stop / Kick Start
In some applications it may be necessary to kick loose the motor i.e.
initial friction, and therefore a kick start can be used. With this
function, a selectable fixed voltage is applied during a settable time.
10:9 Kick Start Level
Path in menu:
Menu/SETTINGS/Functional Settings/
Start/Stop / Kick Level
With this parameter it is possible to set the level of the kick start. It
is active only if kick start is selected.
10:10 Kick Start Time
Path in menu:
Menu/SETTINGS/Functional Settings/
Start/Stop / Kick Time
This parameter makes it possible to set the time of the kick start. It
is active only if kick start is selected.
Parameter
text
Default
value
Setting
range
Description
Kick Start No Yes, No
Selection of
Kick Start
Parameter
text
Default
value
Setting
range
Description
Kick Level 50% 50… 100%
Level of Kick
Start
Parameter
text
Default
value
Setting
range
Description
Kick Time 0.2 s 0.1… 1.5 s
Time for Kick
Start
Figure 7: Kick start