Low Voltage Products & Systems 89
ABB Inc. • 888-385-1221 • www.abb-control.com AC 1006.9 - 5/03
Chapter 7 - Settings and configuration
7:2.4.8 Sequence start
The sequence start function can be used for starting several
motors or multiple speed motors with different parameter
sets such as individual ramp times, initial voltages, current
limits etc.
Up to three individual parameter sets can be used simulta-
neously.
The LOCAL CONTROL menu can not be entered if Se-
quence start is selected.
Number of sequences (No of Seq)
To set parameters related to a sequence start, enter the Seq
Start group.
Select the required number of parameter sets for the appli-
cation.
The following selections are available:
No Sequence start is not activated.
The softstarter is in normal operation.
2 Two different parameter sets will be used.
3 Three different parameter sets will be used.
Press
Store
to save/activate the selected function.
First sequence setting current (1st Set Ie)
Set the current for the first parameter group and press
Store
to save the value.
This parameter will only be displayed if parameter
No of Seq
is set to 2 or 3.
Second sequence setting current (2nd Set Ie)
Set the current for the second parameter group.
Press
Store
to save the value.
This parameter will only be displayed if parameter
No of Seq
is set to 2 or 3.
Figure 31: Sequence start group
Seq. Start
Settings
Functional settings
Start / Stop
Protections
Warnings
Faults
Inputs
Outputs
Fieldbus