10:60 Start ramp, second sequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/2nd Seq. Param./Start Ramp2
This parameter makes it possible to set the start ramp time for the
second parameter set.
10:61 Initial voltage, second sequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/2nd Seq. Param./Init Volt2
This parameter makes it possible to set the initial voltage for the
second parameter set.
10:62 Current limit, second sequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/2nd Seq. Param./Curr Lim2
This parameter makes it possible to set the current limit level for the
second parameter set.
Chapter 10 - Functions
Parameter
text
Default
value
Setting
range
Description
Start Ramp2 10 s
1… 30s,
1… 120s
Second
sequence,
time for start
ramp
Parameter
text
Default
value
Setting
range
Description
Init Volt2 30% 30 70%
Second
sequence,
initial voltage
for start
ramp
Parameter
text
Default
value
Setting
range
Description
Curr Lim2
4xI
e
2.0 5.0xI
e
Second
sequence,
current limit