142 Low Voltage Products & Systems
AC 1006.9 - 5/03 ABB Inc. • 888-385-1221 • www.abb-control.com
Chapter 10 - Functions
10:48 SCR short circuit fault, type of opera-
tion
Path in menu:
Menu/SETTINGS/Functional Settings/
Faults/SCR SC Op
If one or several thyristors are shorted, this parameter makes it
possible to select between two different actions.
Stop– M
Stop– A
The motor stops and a manual reset is
required before restart.
The motor stops and an automatic reset
is performed when the fault disappears.
Parameter
text
Default
value
Setting
range
Description
SCRSCOp Stop-M
Stop-M,
Stop-A
Type of
operation for
SCR short
circuit fault