160 Low Voltage Products & Systems
AC 1006.9 - 5/03 ABB Inc. 888-385-1221 www.abb-control.com
Status Possible cause
Displayed current in LCD does
not correspond to motor current.
Inside Delta connection. If the softstarter is connected Inside
Delta, the current displayed is 58%
of the motor current.
Displayed current in LCD is not
stable.
Themotoristoosmall. Check that the softstarter
corresponds to the motor size.
Increase the load if possible.
Check that softstarter and motor
sizes correspond.
Loading of parameters does not
work properly.
Fieldbus settings. See chapter Fieldbus for actual
fieldbus type.
Solution
Theloadonthemotoristoo
small. (current is out of measuring
range).
Chapter 11 - Troubleshooting
11:3 Start up faults
Power on ProtectionFault
Power on ProtectionFault
(1/( 3))
Status Possible cause
LCD Auto shut off the keypad. Touch any key on the keypad.
Control voltage is not connected. Connect the control voltage
according to the circuit diagram.
Solution