146 Low Voltage Products & Systems
AC 1006.9 - 5/03 ABB Inc. 888-385-1221 www.abb-control.com
10:52 Fieldbus control
Path in menu:
Menu/SETTINGS/Functional Settings/
Fieldbus/Fieldb Ctrl
If the softstarter is going to be used with fieldbus communication, the
fieldbus interface must be activated before any action can be taken.
Warning!
If the motor is running and the parameter Fieldb Ctrl is changed from
No to Yes, this will stop the motor (fieldbus control overrides the
programmable inputs).
If the motor is not running and the parameter Fieldb Ctrl is changed
from Yes to No, this might start the motor if there is a start signal
present.
Chapter 10 - Functions
Parameter
text
Default
value
Setting
range
Description
Fieldb Ctrl No Yes, No
Control of
the
softstarter
with fieldbus