Chapter 10 - Functions
10:63 Setting current, second sequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/2nd Seq. Param./2nd Set Ie
This parameter makes it possible to set the rated motor current for
the second parameter set.
10:64 Start ramp, third sequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/3rd Seq. Param./Start Ramp3
This parameter makes it possible to set the start ramp time for the
third parameter set.
10:65 Initial voltage, second sequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/3rd Seq. Param./Init Volt3
This parameter makes it possible to set the initial voltage for the
third parameter set.
Parameter
text
Default
value
Setting
range
Description
2 Set Ie Ir
9… 1380A
divided into
19
overlapping
ranges
Second
sequence,
current limit
Parameter
text
Default
value
Setting
range
Description
Start Ramp3 10 s
1… 30s,
1… 120s
Third
sequence,
time for start
ramp
Parameter
text
Default
value
Setting
range
Description
Init Volt3 30% 30… 70%
Third
sequence,
initial voltage
for start
ramp