148 Low Voltage Products & Systems
AC 1006.9 - 5/03 ABB Inc. • 888-385-1221 • www.abb-control.com
10:55 Sequence start, number of sequences
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/No of Seq
The softstarter can start motors with up to three different parameter
sets (1st parameter set, 2nd parameter set and 3rd parameter set).
This function can be used for starting motors in a sequence (one by
one) and also for starting two or three speed motors where different
starting parameters are required for each speed.
The LOCAL CONTROL menu can not be entered if Sequence
start is selected.
10:56 Start ramp, first sequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/1st Seq. Param./Start Ramp1
This parameter makes it possible to set the start ramp time for the
first parameter set.
Chapter 10 - Functions
Parameter
text
Default
value
Setting
range
Description
No of Seq No No, 2, 3
Number of
sequences
for sequence
start
Parameter
text
Default
value
Setting
range
Description
Start Ramp1 10 s
1… 30s,
1… 120s
First
sequence,
time for start
ramp