6 Application Instructions API 00-49
DVP-PLC Application Manual
6-26
API Mnemonic Operands Function
16
D FMOV P
Fill Move
Controllers
ES/EX/SS SA/SX/SC EH/SV
Bit Devices Word Devices Program Steps Type
OP
X Y M S K H KnX KnY KnM KnS T C D E F
S
* * * * * * * * ***
D
* * * * * *
n * *
FMOV, FMOVP: 7 steps
DFMOV, DFMOVP: 13 steps
PULSE 16-bit 32-bit
ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV
Operands:
S: Source of data D: Destination of data n: Number of data to be moved
Explanations:
1. If S is used in device F, only 16-bit instruction is applicable.
2. Range of n: 1~ 512 (16-bit instruction); 1 ~ 256 (32-bit instruction).
3. See the specifications of each model for their range of use.
4. The contents in n registers starting from the device designated by S will be moved to n registers starting from
the device designated by D. If n exceeds the actual number of available source devices, only the devices that
fall within the valid range will be used.
5. ES/EX/SS do not support the use of KnX, KnY, KnM, KnS and E, F index register modification.
Program Example:
When X10 = On, K10 will be moved to the 5 consecutive registers starting from D10.
X10
D10 K5FMOV K10
K10
K10
K10
K10
K10
K10
D10
D11
D12
D13
D14
n=5