8 Application Instructions API 100-149
DVP-PLC Application Manual
8-25
API Mnemonic Operands Function
112
D MOVR P
Move Floating Point Data
Controllers
ES/EX/SS SA/SX/SC EH/SV
Bit Devices Word Devices Program Steps Type
OP
X Y M S K H KnX KnY KnM KnS T C D E F
S
D * * * * * *
DMOVR, DMOVRP: 9 steps
PULSE 16-bit 32-bit
ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV
Operands:
SSource floating point data DDestination device
Explanations:
1. S can only be in floating point (FX.XX).
2. See the specifications of each model for their range of use.
3. This instruction is able to enter floating point values directly in S.
4. When the instruction is executed, the content in S is moved directly into D.
When the instruction is not executed,
the content in D will not be modified.
Program Example:
1. User DMOVR instruction to move 32-bit floating point data.
2. When X0 = Off, the content in (D11D10) remains unchanged. When X0 = On, the present value
F1.20000004768372 will be moved to data registers (D11, D10).
X0
DMOVR F1.20000004768372
D10
Remarks:
This instruction only supports ES V6.1, SA/SX_V1.1, SV_V1.2, EH_V1.2, EH2/SV_V1.0 and above versions.