Configuration and Use Manual 53
Required Transmitter Configuration
Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup
6.8 Configuring the discrete input
See the Configuration and Use Manual Supplement for your transmitter for information and
instructions on configuring the discrete input.
6.9 Establishing a meter verification baseline
Note: This procedure applies only if your transmitter is connected to an enhanced core processor and
you have ordered the meter verification application. In addition, ProLink II v2.5 or later is required.
Meter verification is a method of establishing that the flowmeter is performing within factory
specifications. See Chapter 10 for more information about Smart Meter Verification.
Micro Motion recommends performing metere verification several times over a range of process
conditions after the transmitter’s required configuration procedures have been completed. This will
establish a baseline for how widely the verification measurement varies under normal circumstances.
The range of process conditions should include the expected variations in flow rate, temperature,
density, and pressure.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Micro Motion 1000 Series and is the answer not in the manual?

Emerson Micro Motion 1000 Series Specifications

General IconGeneral
BrandEmerson
ModelMicro Motion 1000 Series
CategoryTransmitter
LanguageEnglish

Related product manuals